I'll happily take a single high qualify power supply (which may have internal redundancy FWIW) over 70 much more cheaply made power supplies that stress other parts of my datacenter via sheer inefficiency, and also costs more in aggregate. Nobody drives down the highway with 10 spare tires for their SUV.
The probability of at least a single failure is 1-(1-r)^70.
This is quite high even w/out considering the higher quality of the one supply.
The probability of all 70 going down is
r^70 which is absurdly low.
Let's say r = 0.05 or one failed supply every 20 in a year.
1-(1-r)^70 = 97% r^70 < 1E-91
The high quality supply has r = 0.0005, in between no failure and all failing. If you code can handle node failure, very many, cheaper supplies appears to be more robust.
(Assuming uncorrelated events. YMMV)
Or are the running on SOFCs?
But I’m not debating the merits of this engineering tradeoff - which seems fine, and pretty widely adopted - just its advertisement. The healthcare industry understands the importance of assessing clinical endpoints (like mortality) rather than surrogate measures (like lab results). Whenever we replace “legacy” with “cloud”, it’d be nice to estimate the change in TCO.
The power shelf that keeps the busbar fed will have multiple rectifiers, often with at least N+1 redundancy so that you can have a rectifier fail and swap it without the rack itself failing. Similar things apply to the battery shelves.
In the event that all 32 servers had redundant AC power feeds, you could just install a pair of redundant DC power feeds.
Is this not standard? I vaguely remember that rack severs typically have two PSUs for this reason.
Better have good capacity management so you don't go over 100% on B when that happens! (I've seen it happen and take a DC out).
Who told you there is only one PSU in the power shelf?
Everyone who's doing serious datacenter stuff at scale knows that one of the absolute least efficient, labor intensive and cabling intensive/annoying ways of powering stuff is to have something like a 42U cabinet with 36 servers in it, each of them with dual power supplies, with power leads going to a pair of 208V 30A vertical PDUs in the rear of the cabinet. It gets ugly fast in terms of efficiency.
The single point of failure isn't really a problem as long as the software is architected to be tolerant of the disappearance of an entire node (mapping to a single motherboard that is a single or dual cpu socket config with a ton of DDR4 on it).
We're absolutely aware of the tradeoffs here and have made quite considered decisions!
This creates a single point of failure, trading robustness for efficiency. There's nothing wrong with that, but software/ops might have to accommodate by making the opposite tradeoff. In general, the cost savings advertised by cloud infrastructure should be more holistic.