Re:Oxide Cuts Data Center Power Consumption in Half by glitchcrab on Thursday November 21, 2024 @05:00PM (#42209141)
It's highly dependent on the individual server model and quite often how you spec it too. Most 1U Dell machines I worked with in the past only had a single slot for a PSU, whereas the beefier 2U (and above) machines generally came with 2 PSUs.
Re:Oxide Cuts Data Center Power Consumption in Half by thfuran on Thursday November 21, 2024 @05:25PM (#42209325)
But 2 PSUs plugged into the same AC supply still have a single point of failure.
Re:Oxide Cuts Data Center Power Consumption in Half by glitchcrab on Friday November 22, 2024 @02:05AM (#42211740)
Which is why you have two separate PDUs in the rack which are fed by different power feeds and you connect the server's 2 PSUs to opposing PDUs.
Re:Oxide Cuts Data Center Power Consumption in Half by growse on Friday November 22, 2024 @03:17PM (#42217051)
This works brilliantly, right up to the point where your A side fails, and every single server suddenly doubles their demand on B.

Better have good capacity management so you don't go over 100% on B when that happens! (I've seen it happen and take a DC out).