Re:Oxide Cuts Data Center Power Consumption in Half by shivak on Thursday November 21, 2024 @04:53PM (#42209079)
A DC busbar can propagate a short circuit across the rack, and DC circuit protection is harder than AC. So of course each server now needs its own current limiter, or a cheap fuse.

But I’m not debating the merits of this engineering tradeoff - which seems fine, and pretty widely adopted - just its advertisement. The healthcare industry understands the importance of assessing clinical endpoints (like mortality) rather than surrogate measures (like lab results). Whenever we replace “legacy” with “cloud”, it’d be nice to estimate the change in TCO.

Re:Oxide Cuts Data Center Power Consumption in Half by malfist on Thursday November 21, 2024 @05:59PM (#42209567)
DC circuit protection is absolutely not harder than AC. DC has the advantage in current flowing in only one direction, not two
Re:Oxide Cuts Data Center Power Consumption in Half by paddy_m on Thursday November 21, 2024 @07:02PM (#42209948)
Which makes it much harder to break the circuit vs AC
Re:Oxide Cuts Data Center Power Consumption in Half by wbl on Thursday November 21, 2024 @09:16PM (#42210571)
At 48 volts arcing shorts aren't the concern.