Re:Oxide Cuts Data Center Power Consumption in Half by sidewndr46 on Thursday November 21, 2024 @04:16PM (#42208751)
This isn't even remotely close. Unless all 32 servers have redundant AC power feeds present, you've traded one single point of failure for another single point of failure.

In the event that all 32 servers had redundant AC power feeds, you could just install a pair of redundant DC power feeds.

Re:Oxide Cuts Data Center Power Consumption in Half by gruez on Thursday November 21, 2024 @04:52PM (#42209061)
>Unless all 32 servers have redundant AC power feeds present, you've traded one single point of failure for another single point of failure.

Is this not standard? I vaguely remember that rack severs typically have two PSUs for this reason.

Re:Oxide Cuts Data Center Power Consumption in Half by glitchcrab on Thursday November 21, 2024 @05:00PM (#42209141)
It's highly dependent on the individual server model and quite often how you spec it too. Most 1U Dell machines I worked with in the past only had a single slot for a PSU, whereas the beefier 2U (and above) machines generally came with 2 PSUs.
Re:Oxide Cuts Data Center Power Consumption in Half by thfuran on Thursday November 21, 2024 @05:25PM (#42209325)
But 2 PSUs plugged into the same AC supply still have a single point of failure.
Re:Oxide Cuts Data Center Power Consumption in Half by glitchcrab on Friday November 22, 2024 @02:05AM (#42211740)
Which is why you have two separate PDUs in the rack which are fed by different power feeds and you connect the server's 2 PSUs to opposing PDUs.
Re:Oxide Cuts Data Center Power Consumption in Half by growse on Friday November 22, 2024 @03:17PM (#42217051)
This works brilliantly, right up to the point where your A side fails, and every single server suddenly doubles their demand on B.

Better have good capacity management so you don't go over 100% on B when that happens! (I've seen it happen and take a DC out).

Re:Oxide Cuts Data Center Power Consumption in Half by sidewndr46 on Thursday November 21, 2024 @05:14PM (#42209235)
you could have 15 PSUs in a server. It doesn't mean they have redundant power feeds
Re:Oxide Cuts Data Center Power Consumption in Half by jeffbee on Thursday November 21, 2024 @05:43PM (#42209457)
Rack servers have two PSUs because enterprise buyers are gullible and will buy anything. Generally what happens in case of a single PSU failure is the other PSU also fails or it asserts PROCHOT which means instead of a clean hard down server you have a slow server derping along at 400MHz which is worse in every possible way.