Re:Oxide Cuts Data Center Power Consumption in Half by mycoliza on Thursday November 21, 2024 @06:10PM (#42209634)
The big piece of copper is fed by redundant rectifiers. Each power shelf has six independent rectifiers which are 5+1 redundant if the rack is fully loaded with compute sleds, or 3+3 redundant if the rack is half-populated. Customers who want more redundancy can also have a second power shelf with six more rectifiers.
Re:Oxide Cuts Data Center Power Consumption in Half by hn-throw on Thursday November 21, 2024 @09:35PM (#42210664)
I'm going to assume this is on 3 phase power, but how is the ripple filtered?
Re:Oxide Cuts Data Center Power Consumption in Half by applied_heat on Friday November 22, 2024 @01:24AM (#42211584)
Inductors and capacitors usually