Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by ksec on Sunday August 10, 2025 @03:33AM (#44853455)
It is not like CPU aren't getting higher wattage as well. Both AMD and Intel have roadmap for 800W CPU.

At 50-100W for IO, this only leaves 11W per Core on a 64 Core CPU.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by linotype on Wednesday August 13, 2025 @02:41PM (#44892197)
800 watt CPU with a 600 watt GPU, I mean at a certain point people are going to need different wiring for outlets right?
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by chronogram on Wednesday August 13, 2025 @02:50PM (#44892295)
That's still not much for wiring in most countries. A small IKEA consumer oven is only 230V16A=3860W. Those GPUs and CPUs only consume that much at max usage anyway. And those CPUs are uninteresting for consumers, you only need a few Watts for a single good core, like a Mac Mini has.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by dv_dt on Wednesday August 13, 2025 @03:19PM (#44892637)
So Europe ends up with an incidental/accidental advantage in the AI race?
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by kube-system on Wednesday August 13, 2025 @03:39PM (#44892859)
Consumers with desktop computers are not winning any AI race anywhere.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by atonse on Wednesday August 13, 2025 @03:44PM (#44892907)
All American households get mains power at 240v (I'm missing some nuance here about poles and phases, so the electrical people can correct my terminology).

It's often used for things like ACs, Clothes Dryers, Stoves, EV Chargers.

So it's pretty simple for a certified electrician to just make a 240v outlet if needed. It's just not the default that comes out of a wall.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by kube-system on Wednesday August 13, 2025 @03:54PM (#44893031)
To get technical -- US homes get two phases of 120v that are 180 degrees out of phase with the neutral. Using either phase and the neutral gives you 120v. Using the two out of phase 120v phases together gives you a difference of 240v.

https://appliantology.org/uploads/monthly_2016_06/large.5758...

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by ender341341 on Wednesday August 13, 2025 @04:19PM (#44893339)
Even more technical, we don't have two phases, we have 1-phase that's split in half. I hate it cause it makes it confusing.

Two phase power is not the same as split phase (There's basically only weird older installations of 2 phase in use anymore).

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by kube-system on Wednesday August 13, 2025 @04:28PM (#44893457)
Yeah that's right. The grid is three phases (as it is basically everywhere in the world), and the transformer at the pole splits one of those in half. Although, what are technically half-phases are usually just called "phases" when they're inside of a home.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by ender341341 on Wednesday August 13, 2025 @04:02PM (#44893128)
> So it's pretty simple for a certified electrician to just make a 240v outlet if needed. It's just not the default that comes out of a wall.

It'd be all new wire run (120 is split at the panel, we aren't running 240v all over the house) and currently electricians are at a premium so it'd likely end up costing a thousand+ to run that if you're using an electrician, more if there's not clear access from an attic/basement/crawlspace.

Though I think it's unlikely we'll see an actual need for it at home, I imaging a 800w cpu is going to be for server class CPUs and rare-ish to see in home environments.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by vel0city on Wednesday August 13, 2025 @05:38PM (#44894172)
I don't think many people would want some 2kW+ system sitting on their desk at home anyways. That's quite a space heater to sit next to.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bonzini on Wednesday August 13, 2025 @06:21PM (#44894574)
Also the noise from the fans.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by Tor3 on Thursday August 14, 2025 @01:00AM (#44896879)
I should look at the label (or check with a meter..), but when I run my SGI Octane with its additional XIO SCSI board in active use, the little "office" room gets very hot indeed.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by com2kid on Wednesday August 13, 2025 @06:08PM (#44894446)
> and currently electricians are at a premium so it'd likely end up costing a thousand+

I got a quote for over 2 thousand to run a 24v line literally 9 feet from my electrical panel across my garage to put a EV charger in.

Opening up an actual wall and running it to another room? I can only imagine the insane quotes that'd get.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by Marsymars on Wednesday August 13, 2025 @10:57PM (#44896309)
I kinda suspect there’s a premium once you mention “EV vehicle”, since you’re signalling that you’re affluent enough to afford an EV and have committed to spending the money required to get EV charging at home working, etc. (Kinda like getting a quote for anything wedding related.)

I’m getting some wiring run about the same distance (to my attic, fished up a wall, with moderately poor access) for non-EV purposes next week and the quote was a few hundred dollars.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by tguvot on Thursday August 14, 2025 @12:50AM (#44896841)
the trick is to request 240v outlet for welder. it brings price down to 400 or so.

running to another room will be done usually (at least in usa) through attic or crawlspace. i got it done a few months ago to have dedicated 20A circuit (for my rack) in my work room. cost was around 300-400 as well

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by com2kid on Thursday August 14, 2025 @02:40AM (#44897396)
Labor chargers alone are going to be higher than that in Seattle. Just to have someone come out on a call is going to be 150-200. If it is an independent electrician who owns their own business, maybe 100-150/hr, if they are part of a larger company, I'd expect even more than that.

Honestly I wouldn't expect to pay less than $1000 for the job w/o any markups.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by tguvot on Thursday August 14, 2025 @02:48AM (#44897450)
i live in bay area. i have some doubts that seattle going to be more expensive.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by com2kid on Thursday August 14, 2025 @03:21AM (#44897672)
Handy man prices around here are $65 to $100/hr, and there is a huge wait list for the good ones.

I've gotten multiple quotes on running the 240v line, the labor breakdown was always over $400 alone. Just having someone show up to do a job is going to be almost $200 before any work is done.

When I got quotes from unlicensed people, those came in around $1000 even.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by tguvot on Thursday August 14, 2025 @12:59PM (#44902833)
in bayarea subreddits there are multiple posts talking about EV charger vs welder outlet and how it drops price from 2000 to 500 or so (depends on complexity).

another thing, which is good long term is to a find a local electrician (plumber, etc) who doesn't charge service calls and have reasonable pricing.

no idea about handyman pricing. never used any. for electrical/water/roofing i prefer somebody who is licensed/insured/bonded/etc

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by voxadam on Wednesday August 13, 2025 @03:56PM (#44893065)
Relevant video from Technology Connections:

"The US electrical system is not 120V" https://youtu.be/jMmUoZh3Hq4

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by atonse on Wednesday August 13, 2025 @04:09PM (#44893233)
That's such a great video, like most of his stuff.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by dv_dt on Wednesday August 13, 2025 @04:00PM (#44893105)
Well yes its possible but often $500-1000 to run a new 240v outlet, and that's to a garage for an ev charger. If you want an outlet in the house I dont know how much wall people want to tear up and extra time and cost.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by atonse on Wednesday August 13, 2025 @04:04PM (#44893159)
Sure yeah, I was just clarifying that if the issue is 240v, etc, US houses have the feed coming in. Infrastructure-wise it's not an issue at all.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by the8472 on Wednesday August 13, 2025 @06:04PM (#44894407)
If we're counting all the phases then european homes get 400V 3-phase, not 240V split-phase. Not that typical residential connections matter to highend servers.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bonzini on Wednesday August 13, 2025 @06:20PM (#44894560)
It depends on the country, in many places independent houses get a single 230V phase only.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by buckle8017 on Wednesday August 13, 2025 @03:37PM (#44892828)
In residential power delivery? yes

In power cost? no

I'm literally any other way? also no

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by carlhjerpe on Wednesday August 13, 2025 @05:47PM (#44894251)
In the Nordics we're on 10A for standard wall outlets so we're stuck on 2300W without rewiring (or verifying wiring) to 2.5mm2.

We rarely use 16A but it exists. All buildings are connected to three phases so we can get the real juice when needed (apartments are often single phase).

I'm confident personal computers won't reach 2300W anytime soon though

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bonzini on Wednesday August 13, 2025 @06:19PM (#44894555)
In Italy we also have 10A and 16A (single phase). In practice however almost all wires running in the walls are 2.5 mm^2, so that you can use them for either one 16A plug or two adjacent 10A plugs.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by Tor3 on Thursday August 14, 2025 @12:55AM (#44896861)
In the Nordics (I'm assuming you mean Nordic countries) 10A is _not_ standard. Used to be, some forty years ago. Since then 16A is standard. My house has a few 10A leftovers from when the house was built, and after the change to TN which happened a couple of decades ago, and with new "modern" breakers, a single microwave oven on a 10A circuit is enough to trip the breaker (when the microwave pulses). Had to get the breakers changed to slow ones, but even those can get tripped by a microwave oven if there's something else (say, a kettle) on the same circuit.

16A is fine, for most things. 10A used to be kind of ok, with the old IT net and old-style fuses. Nowadays anything under 16A is useless for actual appliances. For the rest it's either 25A and a different plug, or 400V.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by carlhjerpe on Thursday August 14, 2025 @04:06AM (#44897952)
Let's rephrase: 10A is the effective standard that's been in use for a long long time, if you walk into a building you can assume it has 10A breakers.

On new installations you can choose 10A or 16A so if you're forward thinking you'd go 16 since it gives you another 1300 watts to play with.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by rbanffy on Wednesday August 13, 2025 @05:53PM (#44894304)
> And those CPUs are uninteresting for consumers, you only need a few Watts for a single good core, like a Mac Mini has.

Speak for yourself. I’d love to have that much computer at my disposal. Not sure what I’d do with it. Probably open Slack and Teams at the same time.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by ThunderSizzle on Wednesday August 13, 2025 @08:56PM (#44895641)
> Probably open Slack and Teams at the same time.

Too bad it feels like both might as well be single threaded applications somehow

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by rbanffy on Thursday August 14, 2025 @09:14AM (#44899998)
I could use KVM and open a bunch of instances of each.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jchw on Wednesday August 13, 2025 @02:50PM (#44892289)
At least with U.S. wiring we have 15 amps at 120 volts. For continuous power draw I know you'd want an 80% margin of safety, so let's say you have 1440 Watts of AC power you can safely draw continuously. Power supplies built on MOSFETs seem to peak at around 90% efficiency, but you could consider something like the Corsair AX1600i using gallium nitride transistors, which supposedly can handle up to 1600 watts at 94% efficiency.

Apparently we still have room, as long as you don't run anything else on the same circuit. :)

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by atonse on Wednesday August 13, 2025 @03:46PM (#44892927)
You can always have an electrician install a larger breaker for a particular circuit. I did that with my "server" area in my study, which was overkill cuz I barely pull 100w on it. But it cost nearly zero extra since he was doing a bunch of other things around the house anyway.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by davrosthedalek on Wednesday August 13, 2025 @03:58PM (#44893085)
Larger breaker and thicker wires!
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by atonse on Wednesday August 13, 2025 @04:02PM (#44893138)
I thought you only needed thicker wires for higher amps? Should go without saying, but I am not a certified electrician :-)

I only have a PhD from YouTube (Electroboom)

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jchw on Wednesday August 13, 2025 @04:44PM (#44893624)
The voltage is always going to be the same because the voltage is determined by the transformers leading to your service panel. The breakers break when you hit a certain amperage for a certain amount of time, so by installing a bigger breaker, you allow more amperage.

If you actually had an electrician do it, I doubt they would've installed a breaker if they thought the wiring wasn't sufficient. Truth is that you can indeed get away with a 20A circuit on 14 AWG wire if the run is short enough, though 12 AWG is recommended. The reason for this is voltage drop; the thinner gauge wire has more resistance, which causes more heat and voltage drop across the wire over the length of it, which can cause a fire if it gets sufficiently hot. I'm not sure how much risk you would put yourself in if you were out-of-spec a bit, but I wouldn't chance it personally.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bangaladore on Wednesday August 13, 2025 @06:26PM (#44894613)
Could you not just run a 240 volt outlet on existing wiring built for 110v? Just send l1 and l2 on the existing hot/neutral?
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bri3d on Wednesday August 13, 2025 @06:36PM (#44894703)
You can, 240V on normal 12/2 Romex is fine. The neutral needs to be "re-labeled" with tape at all junctions to signify that it's hot, and then this practice is (generally) even code compliant.

However! This strategy only works if the outlet was the only one on the circuit, and _that_ isn't particularly common.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jchw on Wednesday August 13, 2025 @08:38PM (#44895547)
Although this exists, as a layperson, I've rarely seen it. There is the NEMA 6-15R receptacle type, but I have literally none of those in my entire house, and I've really never seen them. Apparently they're sometimes used for air conditioners. Aside from the very common 5-15R, I see 5-20R (especially in businesses/hospitals), and 14-30R/14-50R for ranges and dryers. (I have one for my range, but here in the midwest electric dryers and ranges aren't as common, so you don't always come across these here. We have LNG ran to most properties.) So basically, I just really don't see a whole lot of NEMA 6 receptacles. The NEMA 14 receptacles, though, require both hots and the neutral, so in a typical U.S. service panel it requires a special breaker and to take up two slots, so definitely not as simple of a retrofit.

(Another outlet type I've seen: I saw a NEMA 7 277V receptacle before. I think you get this from one phase of a 480V three-phase system, which I understand is ran to many businesses.)

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bryanlarsen on Wednesday August 13, 2025 @08:58PM (#44895649)
If you drive an electric car in a rural area you might want to carry around 6-30 and 6-50 adapters because most farms have welders plugged into those and that can give you a quick charge. And also TT-30 and 14-50 adapters to plug in at campgrounds.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bri3d on Wednesday August 13, 2025 @10:21PM (#44896097)
NEMA 6s are extremely common in barns and garages for welders. 6-50 is more common for bigger welders but I’ve also seen 6-20s on repurposed 12/2 Romex as the parent post was discussing used for cheap EV retrofits, compressors, and welders.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by esseph on Wednesday August 13, 2025 @10:49PM (#44896266)
5-20R/6-20R is also somewhat commonly used by larger consumer UPS for your computer, router, etc.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by wat10000 on Thursday August 14, 2025 @04:52AM (#44898271)
NEMA 6 is limiting because there’s no neutral, so everything in the device has to run on 240V. Your oven and dryer want 120V to run lights and electronics, so they use a 14 (or 10 for older installs) which lets them get 120V between a hot and the neutral.

Oddly, 14-50 has become the most common receptacle for non-hardwired EV charging, which is rather wasteful since EV charging doesn’t need the neutral at all. 6-50 would make more sense there.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by bryanlarsen on Thursday August 14, 2025 @09:10AM (#44899951)
Reasons why it's nice to have a 14-50 plug in your garage rather than a 6-50:

1: when an uncle stops by for a visit with his RV he can plug in.

2: the other outlets in your garage are likely on a shared circuit. The 14-50 is dedicated, so with a 14-50 to 5-15 adapter you can more safely plug in a high wattage appliance, like a space heater.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by wat10000 on Thursday August 14, 2025 @11:18AM (#44901435)
1 is why we ended up with 14-50 as the standard, too. Before there was much charging infrastructure, RV parks were a good place to get a semi-fast charge, and that meant a charger with a 14-50 plug.

2 is something I never thought of, I’ll have to keep that in mind.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by viraptor on Wednesday August 13, 2025 @05:48PM (#44894256)
> You can always have an electrician install ...

If you own the house, sure. Many people don't.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by glitchc on Thursday August 14, 2025 @12:19AM (#44896705)
Without upgrsding the wiring to a thicker gauge? That's not code compliant and is likely to cause a fire.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by atonse on Thursday August 14, 2025 @03:34PM (#44904637)
Sorry just to specify, it was more like a 20 amp I think (I will verify), it wasn't like I was going way higher.

I don't remember whether he ran another wire though. It was 5 years ago. Maybe I should not be spreading this anecdote without complete info.

He was a legit electrician that I've worked with for years, specifically because he doesn't cut corners. So I'm sure he did The Right Thing™.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jchw on Thursday August 14, 2025 @04:31PM (#44905341)
There is a chance he did not run new wires if he was able to ascertain that the wire gauge was sufficient to carry 20 amps over the length of the cable. This is a totally valid upgrade though it does obviously require you to be pretty sure you know the length of the entire circuit. If it was Southwire Romex, you can usually tell just by looking at the color of the sheathing on the cable (usually visible in the wallboxes.)
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by glitchc on Thursday August 14, 2025 @08:31PM (#44907349)
If this is north america we're talking about, then 14 gauge is the standard for 120V 15A household circuits. By code, 20A requires 12 gauge. You'll notice the difference right away, it's noticeably harder to bend. Normally a house or condo will only have 15A wires running to circuits in the room. It's definitely not a standard upgrade, the 12 gauge wire costs a lot more per foot, no builder will do it unless the owner forks over extra dough.

Unless you performed the upgrade yourself or know for a fact that the wiring was upgraded to 12 gauge, it's very risky to just upgrade the breaker. That's how house fires start. It's worth it to check. If you know which breaker it is, you can see the gauge coming out. It's usually written on the wire.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jchw on Thursday August 14, 2025 @09:44PM (#44907748)
I was actually under the impression that it is allowed depending on the length of the conductor, but it seems you are right. The NEC Table 15(B)(16) shows the maximum allowed ampacity of 14 AWG cables is 20 amperes, BUT... there is a footnote that states the following:

> * Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an asterisk shall not exceed 15 amperes for No. 14 copper, 20 amperes for No. 12 copper, and 30 amperes for No. 10 copper, after any correction factors for ambient temperature and number of conductors have been applied.

I could've sworn there were actually some cases where it was allowed, but apparently not, or if there is, I'm not finding it. Seems like for 14 AWG cable the breaker can only be up to 15 amperes.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by mrweasel on Thursday August 14, 2025 @02:55AM (#44897484)
In older houses, made from brick and concrete, that can be tricky to do. The only reason I can have my computer on a separate circuit is because we could repurpose the old three phase wiring for a sauna we ripped out. If that had not been the case, getting the wires to the fuse board would have been tricky at best.

New homes are probably worse than old homes through. The wires a just chucked in the space been the outer and inner walls, there's basically no chance of replacing them of pulling new ones. Old houses at least frequently have piping in which the wires run.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jacquesm on Thursday August 14, 2025 @03:56AM (#44897894)
You need to increase the wire diameter as well if you go that route. Running larger breakers on 10A or 15A wiring is a recipe for bad stuff.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by cosmic_cheese on Wednesday August 13, 2025 @03:29PM (#44892731)
Where things get hairy are old houses with wiring that’s somewhere between shaky and a housefire waiting to happen, which are numerous.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by kube-system on Wednesday August 13, 2025 @03:32PM (#44892771)
Yeah, but it ain't nothing that microwaves, space heaters, and hair dryers haven't already given a run for their money.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jchw on Wednesday August 13, 2025 @04:59PM (#44893769)
Hair dryers and microwaves only run for a few minutes, so even if you do have too much resistance this probably won't immediately reveal a problem. A space heater might, but most space heaters I've come across actually seem to draw not much over 1,000 watts.

And even then, even if you do run something 24/7 at max wattage, it's definitely not guaranteed to start a fire even if the wiring is bad. Like, as long as it's not egregiously bad, I'd expect that there's enough margin to cover up less severe issues in most cases. I'm guessing the most danger would come when it's particularly hot outside (especially since then you'll probably have a lot of heat exchangers running.)

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jchw on Wednesday August 13, 2025 @05:03PM (#44893806)
As an old house owner, I can attest to that for sure. In fairness though, I suspect most of the atrocities occur in wall and work boxes, as long as your house is new enough to at least have NM sheathed wiring instead of ancient weird stuff like knob and tube. That's still bad but it's a solvable problem.

I've definitely seen my share of scary things. I have a lighting circuit that is incomprehensibly wired and seems to kill LED bulbs randomly during a power outage; I have zero clue what is going on with that one. Also, often times opening up wall boxes I will see backstabs that were not properly inserted or wire nuts that are just covering hand-twisted wires and not actually threaded at all (and not even the right size in some cases...) Needless to say, I should really get an electrician in here, but at least with a thermal camera you can look for signs of serious problems.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by triknomeister on Wednesday August 13, 2025 @04:00PM (#44893106)
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by t0mas88 on Wednesday August 13, 2025 @03:23PM (#44892675)
A simple kitchen top water cooker is 2000W, so a 1500W PC sounds like no big deal.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by kube-system on Wednesday August 13, 2025 @03:48PM (#44892961)
Kettles in the US are usually 1500W, as the smallest branch circuits in US homes support 15A at 120V and the general rule for continuous loads is to be 80% of the maximum.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by linotype on Wednesday August 13, 2025 @03:59PM (#44893096)
True but kettles rarely run for very long.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by kube-system on Wednesday August 13, 2025 @04:00PM (#44893109)
But computers do, which was why I included that context. You don't really want to build consumer PC >1500W in the US or you'd need to start changing the plug to patterns that require larger branch circuits.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by CyberDildonics on Wednesday August 13, 2025 @05:20PM (#44894001)
Kettles and microwaves are usually 1100 watts and lower, but space heaters and car chargers can be 1500 watts and run for long periods of time.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by wtallis on Wednesday August 13, 2025 @09:21PM (#44895780)
Microwave ovens top out around 1100-1250W output from a ~1500W input from the wall. Apparently there's a fair bit of energy lost in the power supply and magnetron that doesn't make it into the box where the food is.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by Tor3 on Thursday August 14, 2025 @01:08AM (#44896924)
Microwave ovens have a different issue, which I found when I upgraded my breaker board to a modern one in my house. The startup pulse gives a type of load which trips a standard A-type 10A breaker (230V). Had to get those changed to a "slow" type, but even that will trip every blue moon, and if there's something else significant on the same circuit the microwave oven will trip even so, every two weeks or so (for the record, I have several different types of microwave ovens around the house, and this happens everywhere there's a 10A circuit).

The newer circuits in the house are all 16A, but the old ones (very old) are 10A. A real pain, with new TN nets and modern breakers.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by t0mas88 on Saturday August 16, 2025 @05:20AM (#44921666)
Ah, 16A at 230v (3680W) is a normal circuit here. Most appliances work with that, the common exception is electric cooking (using two circuits or 380v two-phase) and EV charging.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by Narishma on Thursday August 14, 2025 @10:43AM (#44900982)
You don't keep the kettle constantly running, unlike a PC.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by tracker1 on Wednesday August 13, 2025 @02:52PM (#44892316)
There already are different outlets for these higher power draw beasts in data centers. The amount of energy used in a 4u "AI" box is what an entire rack used to draw. Data centers themselves are having to rework/rewire areas in order to support these higher power systems.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by orra on Wednesday August 13, 2025 @02:50PM (#44892296)
Laughs in 230V (sorry).
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by AnthonBerg on Thursday August 14, 2025 @04:22AM (#44898088)
ʰᵉₕₑheʰᵉₕₑhe in 400V
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by 0manrho on Wednesday August 13, 2025 @09:09PM (#44895719)
This is a legitimate problem in datacenters. They're getting to the point where a single 40(ish)OU/RU rack can pull a megawatt in some hyperdense cases. The talk of GPU/AI datacenters consuming inordinate amounts of energy isn't just because the DC's are yuge, (although some are), but because the power draw per rack unit space is going through the roof as well.

On the consumer side of things where the CPU's are branded Ryzen or Core instead of Epyc or Xeon, a significant chunk of that power consumption is from the boosting behavior they implement to pseudo-artificially[0] inflate their performance numbers. You can save huge (easily 10%, often closer to 30%, but really depends on exact build/generation) on energy by doing a very mild undervolt and limiting boosting behavior on these cpus and keeping the same base clocks. Intel 11th through 14th gen CPU's are especially guilty of this, as are most Threadripper CPU's. you can often trade single digit or even negligible performance losses (depends on what you're using it for and how much you undervolt/underclock/restrict boosting) for double digit reductions in power usage. This phenomenon is also true for GPU's when compared across the enterprise/consumer divide, but not quite to the significant extent in most cases.

Point being, yeah, it's a problem in data centers, but honestly there's a lot of headroom still even if you only have your common American 15A@120VAC outlets available before you need to call your electrician and upgrade your panel and/or install 240VAC outlets or what have you.

0: I say pseudo-artificial because the performance advantages are real, but unless you're doing some intensive/extreme cooling, they aren't sustainable or indicative of nominal performance, just a brief bit of extra headroom before your cooling solution heat-soaks and the CPU/GPU's throttle themselves back down. But it lets them put the "Bigger number means better" on the box for marketing.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by Panzer04 on Thursday August 14, 2025 @12:34AM (#44896755)
It's not just about better numbers. Getting high clocks for a short period helps in a lot of use cases - say random things like a search. If I'm looking for some specific phrase in my codebase in vscode, everything spins up for the second or two it takes to process that.

Boosting from 4 to 5,5.5 ghz for that brief period shaves a fraction of a second - repeat that for any similar operation and it adds up.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by 0manrho on Saturday August 16, 2025 @10:45AM (#44923913)
Yes, I figured that much would be obvious to this crowd. Thus the "pseudo" part.

The point isn't that there isn't a benefit, it's that you start to pay exponentially more energy per 0.1GHz at a certain point. Furthermore, AMD and Intel were exceptionally aggressive about it in the generations I outlined (AMD would be 7000 series ryzens specifically), leading to instability issues on both platforms due to their spec itself being too aggressive, or AIB partners improperly implementing that spec as the headroom that typically exists from factory stock to push clocks/voltages further was no longer there in some silicon (some of it comes down to silicon lottery and manufacturing defects/mistakes (Intel's oxidation issues for example) but we're really getting into the weeds on this already)

And to clarify: I'm talking specifically of Intel turboboost and AMD's PBO boosting technologies where they boost where they boost well over base clocks, separate from the general dynamic clocking behavior where clocks will drop well below base when not in (heavy) use.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by spacedcowboy on Thursday August 14, 2025 @04:21AM (#44898075)
unless it’s an Apple data center, populated by the server version of the latest ultra chips…
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by deafpolygon on Thursday August 14, 2025 @09:27AM (#44900131)
at that point, they're powered by a bicycle.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by 0manrho on Thursday August 14, 2025 @02:37PM (#44903996)
What makes you think that?

They're small and efficient, that means they can pack large numbers of those into small spaces, resulting in a similar large power draw per volume occupied by equipment in the DC. This is especially true with Apple's "Ultrafusion" tech which they're developing as quasi-analog to Nvidia Grace (Hopper) superchips.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by spacedcowboy on Friday August 15, 2025 @01:29AM (#44908914)
Because I worked on them, before retiring. Yes they’re packed in; no they still don’t draw the same levels of power.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by 0manrho on Saturday August 16, 2025 @10:47AM (#44923930)
Didn't saw they draw the same, I openly acknowledge their more efficient. Said power user per rack unit is trending up. This is true of Apple DC's as well, especially with their new larger/fused chip initiatives. It's an universal industry trends especially with AI compute, and Apple is not immune.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by spacedcowboy on Saturday August 16, 2025 @12:38PM (#44924933)
Let me rephrase to: No, they (collectively) don’t draw the same levels of power. I know what amperage is drawn by each rack. It’s nowhere near as much as was drawn by the older intel-based racks.

And yes, they’re packed densely.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by ciupicri on Thursday August 14, 2025 @01:11PM (#44902987)
How safe is undervolting? Can it cause stability issues?
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by 0manrho on Saturday August 16, 2025 @10:49AM (#44923958)
Far safer than overvolting.

Changing settings can lead to stability issues no matter which way you push it frankly. If you're don't know what you're doing/aren't comfortable with it, probably not worth it.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by latchkey on Friday August 15, 2025 @11:56AM (#44913962)
> They're getting to the point where a single 40(ish)OU/RU rack can pull a megawatt in some hyperdense cases.

Switch is designing for 2MW racks now.

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by esseph on Wednesday August 13, 2025 @10:44PM (#44896237)
Yes and this is something I've been thinking about for awhile.

A computer is becoming a Home Appliance in the it will need 20A wiring and plugs soon, but should move to 220/240v soon anyway (and change the jumper on your standard power supply).

Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by nehalem501 on Thursday August 14, 2025 @12:36AM (#44896769)
It is mostly an issue in countries with 120V mains (I know that in the US 240V outlets exist though). In France for example it is required that standard plugs must be able to deliver at least 16A on each outlet, at the 230V used here, we get 3600W of power, that’s more than enough.
Re:PCIe 8.0 Announced by the PCI-Sig Will Double Throughput ... by jacquesm on Thursday August 14, 2025 @03:55AM (#44897889)
You can up the voltage to 240 and re-use the wiring (with some minor mods to the ends), for double the power. Insulation class should be sufficient. That makes good sense anyway. You may still have an issue if the powersupply can't handle 240/60 but for most of the ones that I've used that would have worked. Better check with the manufacturer to be sure though. It's a lot easier and faster than rewiring.