I think this is an NFPA/NEC[1] standard.
You could look at it another way: circuits are breakered such that you can temporarily peak 25% above their normal capacity without tripping the breaker. I don't know why the standard isn't more conservative, except to guess that it's because typical household/office uses are likely to have low continuous and high intermittent loads (e.g. vacuum cleaner), making it a good trade-off.
[1] USA (and Canada?) only. Anyone know how it is in other countries?
But kika's downthread comment is most on the mark - of course data centers would rather advertise the less relevant "circuit rating" as the number is higher. The load calculations are the same either way.
(btw speaking of the NEC, http://bulk.resource.org/codes.gov/ is a fantastic resource)
I'm not sure why this came about in the first place, though. AFAIK in Europe breakers are rated at 100%.
The breakers in your home breaker box operate the exact same way. A 20A breaker will trip once you exceed a certain threshold, which I believe is 16 or 17. They're rated to go to 20 by the factory, but to prevent problems with overloading and causing fires/explosions/etc, they purposefully break at a lower threshold.
So this isn't just a colo price scam thing, this is the way the world works.
2. A 20 A circuit breaker is allowed to trip at 20.000001 A. Derating the continuous load provides the safety margin for reliable operation, even using inexpensive circuit breakers.
Also, is his concern about earthquakes really warranted? I'd have thought that a DC would have been able to withstand more or less anything thrown its way.