The concern is probably mostly about the power grid. Power problems have caused outages at large colo centers in the last 5 years.
[ Parent
| on HN ]
Re:Going Colo
by kintamanimatt on Tuesday June 26, 2012 @08:00PM
(#4164821)
Why wouldn't they just rate a 20A circuit as 16A if that's all that's usable? What's the benefit to rating it as a 20A circuit if 4A are unusable? I feel like I'm missing something.
Re:Going Colo
by manuscreationis on Wednesday June 27, 2012 @07:54AM
(#4166473)
Believe it or not, this is standard electrical engineering.
The breakers in your home breaker box operate the exact same way. A 20A breaker will trip once you exceed a certain threshold, which I believe is 16 or 17. They're rated to go to 20 by the factory, but to prevent problems with overloading and causing fires/explosions/etc, they purposefully break at a lower threshold.
So this isn't just a colo price scam thing, this is the way the world works.
Re:Going Colo
by tedunangst on Tuesday June 26, 2012 @10:47PM
(#4165261)
Peak draw is less than typical draw. If the fuse blew at 16A, you'd only be able to use 12A. So they give you some headroom. But if everybody draws at 20A all the time, the building melts down. Soft quotas vs hard quotas.
Because it looks better in the pricelist? 20A for $500 is better than 15A for $500.
Re:Going Colo
by Daniel_Newby on Tuesday June 26, 2012 @10:47PM
(#4165264)
1. As mmt mentions in another comment, that's the way the U.S. safety codes rate circuit capacity.
2. A 20 A circuit breaker is allowed to trip at 20.000001 A. Derating the continuous load provides the safety margin for reliable operation, even using inexpensive circuit breakers.