Not piling on AWS. These things happen and I’m sure everyone involved is working to improve things. Yes, everyone should deploy in multiple availability zones.
My 2 cents. Outages happen. Network glitches happen. Bad configs and bad updates happen. However, power issues should not really happen. One of the primary cost saving areas of going to the cloud is not having to do on-prem power, such as UPS, generators, maintenance etc. Not having to do on-prem cooling is another thing. These should be solved from the customer’s perspective when going into a professional data center and are the things you don’t want to worry about anymore.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by ksec on Thursday December 23, 2021 @04:20PM
(#29666607)
Yes. I expect software and network glitches because they are complicated and error prone. But I fully expect hardware and power redundancy. Even if they were down it shouldn't "kill" them. At least not on AWS, the biggest and arguably best DC running in the world. But it did.
This suggest to me DataCenter, as an infrastructure and building on itself still have plenty of room for improvements.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by kazen44 on Thursday December 23, 2021 @03:33PM
(#29666140)
Getting power right in a DC takes a ton of preventative maintenance. (doing black building tests, make sure there are working load tests which occur frequently, managing UPS battery health etc).
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by spenczar5 on Thursday December 23, 2021 @04:41PM
(#29666840)
Yes, it's hard work... but it's work AWS should be great at. Like, really great at.
I used to work at AWS. The most worked-up I ever saw Charlie Bell (the de facto head of AWS engineering) was in the weekly operations meeting, going over a postmortem which described a near-miss as several generators failed to start properly in a power interruption. In this meeting - with nearly 1,000 participants! - Charlie got increasingly irate about the fact that this had happened. For the next few weeks, details of some sort of flushing subsystem for backup generators was an every-time topic.
Sadly, Charlie left AWS and now works at Microsoft. I can't help but wonder what that operations meeting is like now without him.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by mgsouth on Thursday December 23, 2021 @04:56PM
(#29666969)
Slamming on the brakes can be hard on the electronics. It causes large, high-speed voltage or current spikes that kill (old, tired) components before the spikes can be clamped. Can be made worse by old electolytic caps that no longer filter effectively. Especially hard on power supply diodes and mosfets.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by Spivak on Thursday December 23, 2021 @05:22PM
(#29667178)
Which is why if you realize that your hard drive is failing the worst thing you can do is cut the power [1]. You get your data off that box as fast as possible.
[1] Yes yes always have backups, and RAID, and replication something about not being able to count that low. Betcha most'a'ya don't have any of that on your MBP though except for a maybe a backup that lags hours behind your work.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by CoastalCoder on Thursday December 23, 2021 @07:24PM
(#29668305)
> Slamming on the brakes can be hard on the electronics. It causes large, high-speed voltage or current spikes that kill (old, tired) components before the spikes can be clamped.
Suppose that the "slamming on the brakes" here is that the power lines connecting a data center to the grid get physically cut. I can see how that would cause a power spike on the grid side of the cut, but would it really create a spike on the datacenter side of the cut?
Or assuming that the wires in a cable aren't cut exactly simultaneously, does it depend on the particular phases of the AC power at the time of each wire in the cable being cut?
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by R0b0t1 on Thursday December 23, 2021 @07:37PM
(#29668430)
Any change in the state of an inductive load causes kickback. If you sever the lines running to a building, the generator side gets the most kick, but even a fully passive device gets a kick from the collapsing field in the wires servicing it.
The motors generate appreciable back EMF when suddenly unpowered.
Likewise an SMPS is an inductive load. Spikes from power supplies going off is probably what killed the disks, assuming they didn't just decide not to power on. Some disks will run for 10 years but power them off once and they don't come back up.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by SteveNuts on Thursday December 23, 2021 @03:13PM
(#29665960)
In my experience it's common when there's a full power down of a large data center like this. In 2013 the company I was working at had an unplanned power outage which took out 200 spinning drives, and 18
servers. I think the motors in the drives are fine running at constant speed but don't have the juice to spin up from a dead stop.
I remember IBM was renting private planes to get us replacement hardware from around the country (we were a very large customer).
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by lamontcg on Friday December 24, 2021 @01:00PM
(#29675909)
I worked at Amazon from 2001-2006 and there were a couple of datacenter-wide power outages during my time and there was always some machines that never came back. It is just a numbers game. When you have thousands of servers affected some small fraction just don't survive the forced power cycle.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by jbergens on Thursday December 23, 2021 @05:15PM
(#29667125)
A very long time ago I worked for a medium sized company and there was a power outage. The servers were in a room in our building but they had ups power. The problem was that the ups's were broken/malfunctioning and the servers needed to do a disk check after an unplanned reboot. It took hours before we could work again even though most drives survived.
This was also before git so we could not reach the central version control system and could not commit any code. I think all code and workspaces were on servers that was not up yet.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by emptybottle on Thursday December 23, 2021 @04:33PM
(#29666745)
It can be a number of things, but often times it's the thermal cycle and wear on the components.
After letting devices (especially that rarely do this) cool, and then bringing them back up to temperature some percentage of components may fail or operate out of spec.
And mechanical parts have similar issue. A motor that's been happily running for months/years may not restart after being stopped.
It's also possible that a power fault itself could damage hardware, although in my experience this type of issue is far less common.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by michaelrpeskin on Thursday December 23, 2021 @03:43PM
(#29666235)
This might be old lore, but I remember many years ago that someone told me that when a spinning disk has been up to temperature for a long time there's a bit of lubricant that is vaporized and evenly distributed everywhere (like the halides in your halogen headlamps). But when it stops spinning that stuff cools down and gets sticky and ends up sticking the heads to the disk so that it can't get going anymore.
Don't know the truth to that, but it seemed like a reasonable explanation at the time.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by _3u10 on Thursday December 23, 2021 @03:47PM
(#29666278)
Think of it like a car with a starter wearing out, at some point you turn the engine off and it never starts up again, until you replace the starter. Similarly bad batteries, corrosion on terminals, etc. Startup is a much different workload on electronics and in the case of HDDs mechanical devices than running.
I have an old fan that will need replacing one day that takes about 15 minutes to reach full speed as the bearings are gone. Everytime I turn it off I wonder if the next time I turn it on it will be time to replace it.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by wdfx on Thursday December 23, 2021 @04:33PM
(#29666739)
It's just the numbers. Eventually all the hardware will fail. Some of that hardware will require a specific set of conditions to fail. Such a condition may be current inrush from being powercycled. Given the scale of a data centre and powercycling it all at once, then some will fail due to that condition.
Further to that thought, there must be hardware in that centre which is failing and being replaced all the time due to other conditions, we just won't hear about it because it's part of normal maintenance.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by prpl on Thursday December 23, 2021 @06:35PM
(#29667877)
I’m sure temperature variation has something to do with it in some cases. Most parts, even when cooled, are well above room temperature for years on end, a loss of power can drop them to room temp relatively quickly
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by zkirill on Thursday December 23, 2021 @04:23PM
(#29666646)
Have there been any incidents that affected more than one AZ?
AWS RDS in multi-AZ deployment gives you two availability zones. Aurora gives you three. What kind of scenario would be used to justify three AZ’s for the purposes of high availability?
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by Jweb_Guru on Thursday December 23, 2021 @04:29PM
(#29666699)
Aurora isn't really designed to handle the total failure of two availability zones (not short term, anyway). It's designed to handle one AZ + one additional node failure (which is reasonably likely to happen on large instances due to data from a single database being striped across up to 12,800 machines per AZ). Due to how quorum systems work the "simplest" way they decided to handle that was six replicas per 10 GiB segment across 3 AZs, with three of the replicas being log-only and three designated as full replicas (which is the lowest number of full replicas you can have given their failure model, and hitting that lower bound does require you to deploy across 3 AZs). If any three of the nodes are dead (log-only or otherwise), write traffic is stopped until they can bring up a fourth node, though there is some support for backup 3-of-4 quorums for very long-term AZ outages.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by gundmc on Thursday December 23, 2021 @03:36PM
(#29666169)
Rare to see power issues at a modern data center cause downtime. All of those racks should have UPS and batteries to sustain during an outage until the automatic transfer switch can fail over to a redundant system or generator. Would be interested in reading more about what happened here.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by electroly on Thursday December 23, 2021 @03:42PM
(#29666232)
In previous postmortems[0] they've mentioned their UPSes. They definitely have them. They don't seem to write a lot of postmortems, though. I'm not sure whether we should expect one for this event.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by testemailfordg2 on Thursday December 23, 2021 @07:13PM
(#29668218)
Not an expert, but a more frequent and controlled power cycle of servers with HDD can make sure not a lot of servers go down in one go, when events like these happen. Also, gives you chance to identify patterns...
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by psanford on Thursday December 23, 2021 @02:30PM
(#29665526)
I would stay away from any company that thinks "we need to go multicloud" as a response to this outage. This affected a single az in a single region. If it caused you downtime or a partial outage, it means you are not fully resilient to single az failures. The correct thing is to fix your application to handle that.
If you can't handle a single az failure there is no way you are going to handle failing over across different cloud providers correctly.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by nonane on Thursday December 23, 2021 @03:43PM
(#29666238)
> This affected a single az in a single region. If it caused you downtime or a partial outage, it means you are not fully resilient to single az failures.
This is not true. Amazon is not being upfront about what happened here. It was simply not a single AZ failure. Our us-east-1 ELB load balancers were hosed and were unable to direct traffic to other AZs - they simply stopped working an were dropping traffic. We tried creating load balancers in different AZs and that didn't work either.
How can you be resilient to single AZ failures if load balancers stop working region wide during a single AZ outage?
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by acdha on Thursday December 23, 2021 @04:36PM
(#29666780)
Did your TAM go into any details on that? Over a couple hundred load-balancers, the only issue we had was taking longer to register new instances and that affected only a couple of them. Running services weren't interrupted, latency remained, etc. which is what I'd expect for a single AZ failure.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by dragonwriter on Thursday December 23, 2021 @03:25PM
(#29666067)
> If it caused you downtime or a partial outage, it means you are not fully resilient to single az failures.
Given the number of AWS global services that have dependencies on infra in US-EAST-1 (and, from the impacts of this and other past outages, seen vulnerable to single-AZ failures in US-EAST-1) that's...less avoidable for certain regions/AZs than one might naively expect. Most clouds seem to have at least some degree of this kind of vulnerability.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by luhn on Thursday December 23, 2021 @03:18PM
(#29666009)
To be fair though, from what I heard AZ outage caused an EC2 API brownout, so people couldn't launch new instances in the other AZs. That put a wrench in a lot of multi-AZ architectures.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by profmonocle on Thursday December 23, 2021 @02:46PM
(#29665703)
Egress fees can make replicating databases, storage buckets, etc. between clouds very expensive. Multi-region is a much more affordable option. Multi-region outages aren't unheard of among the major cloud operators, but they're less common than single-AZ or single-region outages.
IMO, most companies just aren't sensitive enough to downtime that multi-AZ + multi-region deployment within a single cloud provider isn't good enough.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by isbvhodnvemrwvn on Thursday December 23, 2021 @06:12PM
(#29667667)
You'd have to go worse than lowest common denominator. To have active-active replication you need to take the cost of latency between the different DCs of the various providers, and this thing will kill performance.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by beermonster on Thursday December 23, 2021 @02:58PM
(#29665806)
As large cloud outages become more frequent and the impact greater each time, I feel it’s more likely people will reconsider moving workloads off-prem.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by karmasimida on Thursday December 23, 2021 @08:12PM
(#29668786)
Infra is pure cost center.
A few hours downtime is not going to justify double cost, and worse whose benefits can only be demonstrated during those few hours.
It will get shutdown immediately.
And what is more important, corporate world really don't care that much about downtime, not as much as they care about who to assign the blame, in this case AWS is a perfect irresistible externality much like a natural disaster.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by jacquesm on Thursday December 23, 2021 @03:22PM
(#29666048)
To forestall that reply: I did think about it before hitting the reply button. I've seen a couple of large scale DC power outages in my 35 years of IT work. The vast majority of the hardware came through just fine. But older data centers with gear that has been running uninterrupted for many years tend to have at least some hardware that simply won't come up again, due to a variety of reasons. One can be that the on-board batteries have gone bad, which nobody noticed until the power cycle. Another is that some harddrives function well as long as they keep spinning but that has worn a nasty little spot on the bearing that keeps the spindle aloft. When it spins down, depending on the orientation it may not be able to start back up again, it may even crash while spinning down. Powercycle enough gear that has been running for years and you will most likely lose at least some small fraction of it. You could do it the next day after taking care of those and everything would likely be fine.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by acdha on Thursday December 23, 2021 @04:21PM
(#29666624)
Hopefully, but those aren't perfect. Large data centers regularly test those because things can go wrong with any of the UPS, generator[1], or the distribution hardware which switches between the line and generator power. One of the longer outages I've seen was when the distribution hardware itself failed and burnt out multiple parts which the manufacturer did not have sufficient spares in our region.
AWS has a lot of very skilled professionals who are quite familiar with those issues so I'd be quite surprised if it turned out to be something that simple but you always want to have a contingency plan you've tested for what happens if core infrastructure like that fails and takes multiple days to recover.
1. One nasty example: fuel issues which aren't immediately obvious so someone doing a 5 minute test wouldn't learn that the system wasn't going to handle an outage longer than that.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by jacquesm on Thursday December 23, 2021 @04:18PM
(#29666594)
I've seen plenty of UPS's fail, and generator failover is that moment when everybody stands there with their fingers crossed.
None of those things are fool proof and in case of a large scale outage, especially one that lasts more than a couple of minutes there is a fair chance that you will find the limitations of some of your contingency plans.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by X-Istence on Thursday December 23, 2021 @03:50PM
(#29666303)
Having worked in datacenter where servers were running for 5+ years in racks, when the datacenter went dark due to a UPS going up in flames there were definitely systems that did not come back online.
Most notably we had a large NetApp array that would not boot, once we replaced the controllers we had lost 13 out of the 60 hard drives in the array. They would no longer spin up. Like physically seized. Because they had been spinning for so long, they would have likely kept spinning just fine, but with power gone, it was done.
Fans are another fun one, anything with ball bearings really. Power supplies are another issue, due to the sudden large inrush of power when the switch was flipped back to on, some power supplies had their capacitors go up in smoke.
This is not rare, this a common occurrence. When you have an absolutely massive footprint with thousands upon thousands of servers, that have been running for a long time, there will be things that just don't come back once they have stopped running or when the electricity is gone.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by jdsully on Thursday December 23, 2021 @02:50PM
(#29665739)
Starting up is hard on electronics due to the inrush current. There may be marginal devices just barely operating that will not survive a reboot. Things like bad capacitors aren’t always detectable during steady state.
At AWS scale it’s highly likely there are more than a few of these.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by daneel_w on Thursday December 23, 2021 @02:56PM
(#29665791)
Did you think this over before hitting the reply button? Can you imagine any server or networking brand surviving if its products were at substantial risk of dying when powering up or cycling? Have you ever heard of common consumer grade computer equipment regularly dying from it? No? Not me either.
It's really common to find thyristors in devices to limit in-rush current, even in cheap electronics. You can bet that PSUs in data center equipment use them.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by sonofhans on Thursday December 23, 2021 @03:07PM
(#29665882)
It's a scale problem. We're not talking about "substantial risk" or "regularly dying." At AWS scale even 0.01% cold start failure is noticeable. It's not possible to guarantee perfect operation of each system or component; physical things wear out. If you can find a way to avoid cold-start failure 100% of the time your product would be valuable to many businesses.
Also:
> Did you think this over before hitting the reply button?
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by hhh on Thursday December 23, 2021 @03:39PM
(#29666199)
I don’t know if it’s intentional, but your comment comes off very hostile.
Recently we has a violent power outage where I work due to the tornados in the midwest. A few of our facilities have industrial hardware with batteries that will last for 72 hours and after that point it’s a world of unknowns what will happen. The batteries died after a lot of effort to try and restore power, but everything came up just fine.
However, a random Cisco switch elsewhere in the building had at least one power supply fail.
This was in one facility where most of these have been running for 4+ years straight (12 years for the system with a 72 hour battery.)
I find it hard to imagine that in the scale of even one AZ that it wouldn’t be possible that at least one system has this happen.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by acdha on Thursday December 23, 2021 @04:08PM
(#29666499)
> Did you think this over before hitting the reply button? Can you imagine any server or networking brand surviving if its products were at substantial risk of dying when powering up or cycling?
This is hostile enough that I'd have trouble squaring it with the site guidelines.
It's especially bad because, as others have been saying, your belief isn't supported by real lived experience for many of us. A data center has enough devices that even a low probability error rate will fairly reliably happen, and that doesn't usually hurt the manufacturer's reputation because they never promised 100% and will replace it under warranty. I've seen this with hard drives especially but also things like power supplies and on-board batteries, and even things like motherboards where a cooling/heating cycle was enough to unseat RAM or cause hairline fractures in solder traces.
This can be especially bad with unplanned power outages if the power doesn't instantly go out and stay out for the duration. Especially for hard drives hitting the power up/down cycle a few times was a good way to have extra failures.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by jeffbee on Thursday December 23, 2021 @03:58PM
(#29666397)
> Have you ever heard of common consumer grade computer equipment regularly dying from it?
You have outed yourself as someone with zero experience operating computers, either individually or at scale. Computers have moving parts, whether fans or hard disk drives. Just because those were moving doesn't mean they will begin moving again from a dead stop. There are also things like dead cmos/nvram batteries that can prevent machines from automatically starting when power is applied.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by dpratt on Thursday December 23, 2021 @03:32PM
(#29666131)
And when you have 500,000 copies of something, most of which have been in use for some appreciable fraction of their effective lifetime, it doesn’t have to be “common” to occur to some fraction of them.
The post you’re responding to never implied that it happens to _most_ of them, or even many of them, just that when you have a gigantic farm, it’s not unreasonable to see a small handful of hardware instances release up their magic smoke when they’re all coming back from being powered down.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by unionpivo on Friday December 24, 2021 @10:53AM
(#29674574)
Pretty much anyone who has worked in datacenter disagrees with you. Your assumptions that you know better than people working there are arrogant to extreme.
If electronics (not just computer) is going to fail its almost always at power on or power off.
And since DC is one big electronics warehouse, stuff breaks. Old spinning drives were most prone to this, with power supply and motherboards being second.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by KronisLV on Thursday December 23, 2021 @06:03PM
(#29667564)
Right now i run my homelab on consumer hardware in addition to my cloud VPSes.
Due to me not having that much free space and also enjoying a good night's sleep, i have cron set up to put the servers offline (rtcwake) while i'm sleeping, so that they wouldn't just go on droning in the background and to start up in the morning.
Since they do this every day with no exceptions, that's a decent amount of power cycling, in addition to them working all the time otherwise, which has been going on for about 5 years or so.
So essentially each of them has been on for about 30'000 - 35'000 hours and has power cycled around 1800 - 3600 times, because for the longest time i've had a cron restart set up right after the rtcwake sleep period finishes, due to some odd bug in the kernel that otherwise caused their CPUs to get stuck at 100% usage after waking up.
Over these 5 or so years, i've had:
- 2 PSUs die (possibly one due to a power surge though, before i had UPSes in front of them), seemed to work fine but then one morning didn't start up
- 2 HDDs die (Seagate Barracuda 1 TBs, each box has 2-3 of them), typically this isn't abrupt, but the HDDs lose power when trying to spin up and loop like that for a while before eventually deciding to work, before eventually not being able to do that anymore at all; oddly enough, Clonezilla could still mirror such a disk after a few attempts
- 1 motherboard die (not sure precisely why, then again, for a while in my university i had the servers (without cases) up next to a slighty ajar window, even in winter as well as in summer, while they were otherwise only passively cooled (x86, but 35W TDP 200 GEs)
- some problems with bearings, once in a cheap CPU fan before i had passive cooling and then again in one of the current PSU fans, sometimes when starting up it sounds like a miniature chainsaw (checked the fan, isn't actually seized up or anything, just cheap bearings)
- some problems with the power button (well, more like the pins, since i didn't have a proper button at one point, just a screwdriver to close the circuit with), though i solved that by closing the circuit on the ATX connector itself by putting a little wire in there
All of the failures have happened around power cycling, never in the middle of otherwise normal operation.
To my surprise, nothing has actually melted or caught fire, the last time when anything close to that happened was ages ago with my 9800 GT GPU which for some reason started getting really bad thermals (90 degrees C) and so i had to reflow solder it in the oven a few times, before eventually it just refused to work and artifacted out on boot. Or maybe i could mention a MOLEX connector stopping working, but i might just have a splitter in there due to not enough SATA connections from the PSU, something that people typically advise against.
So, to sum all of that up, yes, consumer hardware will definitely die from regular use under normal circumstances, probably moreso with regular power cycling of parts that aren't really made for that (especially the regular HDDs, which seemed to die right after restarts). Also, my case might be an outlier (and a sample size of 1), due to me not caring that much in university about keeping the servers in a good environment, but i bet that most consumer hardware has to deal with sub-optimal conditions in one way or another - accumulation of dust, bad airflow, air humidity, ambient temperature and power grid fluctuations all should also be taken into account.
I actually had to stagger the startup times for my servers, since otherwise they'd max out their power draw at the same time in the morning (e.g. when launching Docker containers and spinning up VMs), which also lead to some weirdness. Of course, the quality of the parts themselves probably also matters (like a reputable brand PSU vs the cheaper options that i could afford) as much as how they're used (prolonged periods of full load while everything starts up), as do other factors, like vibrations of the HDDs, for example.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by kube-system on Thursday December 23, 2021 @03:00PM
(#29665824)
I am not sure whether or not inrush current (or thermal cycling, or something else) is to blame, but server equipment in data centers has been fairly well documented to exhibit increased hardware failure rates after outages.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by X-Istence on Thursday December 23, 2021 @03:52PM
(#29666326)
Having had to restore a NetApp cluster from backup because the disks would no longer spin up after having been running for 4+ years... yup. The hardware was fully working and according to all internal metrics was still perfectly good, but a power outage and they never came back up.
Re:AWS power failure in US-EAST-1 region killed some hardwar...
by joshuamorton on Thursday December 23, 2021 @04:06PM
(#29666480)
Yes, its a fairly well known issue at datacenter scale that if you power-cycle everything, some percentage of things won't turn back on (I recall something like 1% of HDDs just failing to work again being the number quoted at me). This obviously isn't the case for fresh new HDDs, but ones that have been spinning continuously for a years.
My 2 cents. Outages happen. Network glitches happen. Bad configs and bad updates happen. However, power issues should not really happen. One of the primary cost saving areas of going to the cloud is not having to do on-prem power, such as UPS, generators, maintenance etc. Not having to do on-prem cooling is another thing. These should be solved from the customer’s perspective when going into a professional data center and are the things you don’t want to worry about anymore.
This suggest to me DataCenter, as an infrastructure and building on itself still have plenty of room for improvements.
I used to work at AWS. The most worked-up I ever saw Charlie Bell (the de facto head of AWS engineering) was in the weekly operations meeting, going over a postmortem which described a near-miss as several generators failed to start properly in a power interruption. In this meeting - with nearly 1,000 participants! - Charlie got increasingly irate about the fact that this had happened. For the next few weeks, details of some sort of flushing subsystem for backup generators was an every-time topic.
Sadly, Charlie left AWS and now works at Microsoft. I can't help but wonder what that operations meeting is like now without him.
Leading up to Y2K, I remember concerns about spinning hard disks not being able to start up again.
And if the power is flaky with spikes and brown-outs, I understand that's a problem.
But is either of those relevant to AWS?
Here's a few references at random:
https://vbn.aau.dk/ws/portalfiles/portal/108034396/ESREF2013...
https://www.infineon.com/dgdl/s30p5.pdf?fileId=5546d46253360...
https://www.sciencedirect.com/science/article/pii/S003811010...
[1] Yes yes always have backups, and RAID, and replication something about not being able to count that low. Betcha most'a'ya don't have any of that on your MBP though except for a maybe a backup that lags hours behind your work.
Suppose that the "slamming on the brakes" here is that the power lines connecting a data center to the grid get physically cut. I can see how that would cause a power spike on the grid side of the cut, but would it really create a spike on the datacenter side of the cut?
Or assuming that the wires in a cable aren't cut exactly simultaneously, does it depend on the particular phases of the AC power at the time of each wire in the cable being cut?
The motors generate appreciable back EMF when suddenly unpowered. Likewise an SMPS is an inductive load. Spikes from power supplies going off is probably what killed the disks, assuming they didn't just decide not to power on. Some disks will run for 10 years but power them off once and they don't come back up.
I remember IBM was renting private planes to get us replacement hardware from around the country (we were a very large customer).
After letting devices (especially that rarely do this) cool, and then bringing them back up to temperature some percentage of components may fail or operate out of spec.
And mechanical parts have similar issue. A motor that's been happily running for months/years may not restart after being stopped.
It's also possible that a power fault itself could damage hardware, although in my experience this type of issue is far less common.
* increased failure rates of drives (or other hardware) due to thermal cycling
* cache power failures leading to corrupted data
* previously unknown failures in recovery processes (like firmware bugs that might be described as a "hardware problem")
* cooling failures leading to hardware failure
Most of these are pretty rare issues, but it becomes more probable to happen at least once when you're running freekin' us-east-1
Don't know the truth to that, but it seemed like a reasonable explanation at the time.
I have an old fan that will need replacing one day that takes about 15 minutes to reach full speed as the bearings are gone. Everytime I turn it off I wonder if the next time I turn it on it will be time to replace it.
Further to that thought, there must be hardware in that centre which is failing and being replaced all the time due to other conditions, we just won't hear about it because it's part of normal maintenance.
TLDR if electronics are near-death, a power cycle is likely to kick it over the edge.
AWS RDS in multi-AZ deployment gives you two availability zones. Aurora gives you three. What kind of scenario would be used to justify three AZ’s for the purposes of high availability?
[0] https://aws.amazon.com/premiumsupport/technology/pes/
If you can't handle a single az failure there is no way you are going to handle failing over across different cloud providers correctly.
This is not true. Amazon is not being upfront about what happened here. It was simply not a single AZ failure. Our us-east-1 ELB load balancers were hosed and were unable to direct traffic to other AZs - they simply stopped working an were dropping traffic. We tried creating load balancers in different AZs and that didn't work either.
How can you be resilient to single AZ failures if load balancers stop working region wide during a single AZ outage?
Given the number of AWS global services that have dependencies on infra in US-EAST-1 (and, from the impacts of this and other past outages, seen vulnerable to single-AZ failures in US-EAST-1) that's...less avoidable for certain regions/AZs than one might naively expect. Most clouds seem to have at least some degree of this kind of vulnerability.
Not advocating for multi-cloud though...
IMO, most companies just aren't sensitive enough to downtime that multi-AZ + multi-region deployment within a single cloud provider isn't good enough.
By definition, you would have to either go lowest-common-denominator, or build complicated facades in front of like services.
If you're going lowest-common-denominator, then multi-old-school-hosting would be far cheaper.
vp: no.
A few hours downtime is not going to justify double cost, and worse whose benefits can only be demonstrated during those few hours.
It will get shutdown immediately.
And what is more important, corporate world really don't care that much about downtime, not as much as they care about who to assign the blame, in this case AWS is a perfect irresistible externality much like a natural disaster.
Disclaimer: Ex-AWS employee
No. Not even rarely. If they lost hardware because of this something much different than just loss of power happened on their servers' mains rails.
AWS has a lot of very skilled professionals who are quite familiar with those issues so I'd be quite surprised if it turned out to be something that simple but you always want to have a contingency plan you've tested for what happens if core infrastructure like that fails and takes multiple days to recover.
1. One nasty example: fuel issues which aren't immediately obvious so someone doing a 5 minute test wouldn't learn that the system wasn't going to handle an outage longer than that.
None of those things are fool proof and in case of a large scale outage, especially one that lasts more than a couple of minutes there is a fair chance that you will find the limitations of some of your contingency plans.
Most notably we had a large NetApp array that would not boot, once we replaced the controllers we had lost 13 out of the 60 hard drives in the array. They would no longer spin up. Like physically seized. Because they had been spinning for so long, they would have likely kept spinning just fine, but with power gone, it was done.
Fans are another fun one, anything with ball bearings really. Power supplies are another issue, due to the sudden large inrush of power when the switch was flipped back to on, some power supplies had their capacitors go up in smoke.
This is not rare, this a common occurrence. When you have an absolutely massive footprint with thousands upon thousands of servers, that have been running for a long time, there will be things that just don't come back once they have stopped running or when the electricity is gone.
At AWS scale it’s highly likely there are more than a few of these.
It's really common to find thyristors in devices to limit in-rush current, even in cheap electronics. You can bet that PSUs in data center equipment use them.
Also:
> Did you think this over before hitting the reply button?
This is ad hominem, and we should avoid it here.
Recently we has a violent power outage where I work due to the tornados in the midwest. A few of our facilities have industrial hardware with batteries that will last for 72 hours and after that point it’s a world of unknowns what will happen. The batteries died after a lot of effort to try and restore power, but everything came up just fine.
However, a random Cisco switch elsewhere in the building had at least one power supply fail.
This was in one facility where most of these have been running for 4+ years straight (12 years for the system with a 72 hour battery.)
I find it hard to imagine that in the scale of even one AZ that it wouldn’t be possible that at least one system has this happen.
This is hostile enough that I'd have trouble squaring it with the site guidelines.
It's especially bad because, as others have been saying, your belief isn't supported by real lived experience for many of us. A data center has enough devices that even a low probability error rate will fairly reliably happen, and that doesn't usually hurt the manufacturer's reputation because they never promised 100% and will replace it under warranty. I've seen this with hard drives especially but also things like power supplies and on-board batteries, and even things like motherboards where a cooling/heating cycle was enough to unseat RAM or cause hairline fractures in solder traces.
This can be especially bad with unplanned power outages if the power doesn't instantly go out and stay out for the duration. Especially for hard drives hitting the power up/down cycle a few times was a good way to have extra failures.
Unscheduled power outages can be even worse
You have outed yourself as someone with zero experience operating computers, either individually or at scale. Computers have moving parts, whether fans or hard disk drives. Just because those were moving doesn't mean they will begin moving again from a dead stop. There are also things like dead cmos/nvram batteries that can prevent machines from automatically starting when power is applied.
Yes, absolutely.
The post you’re responding to never implied that it happens to _most_ of them, or even many of them, just that when you have a gigantic farm, it’s not unreasonable to see a small handful of hardware instances release up their magic smoke when they’re all coming back from being powered down.
MTBF is a thing.
If electronics (not just computer) is going to fail its almost always at power on or power off.
And since DC is one big electronics warehouse, stuff breaks. Old spinning drives were most prone to this, with power supply and motherboards being second.
Due to me not having that much free space and also enjoying a good night's sleep, i have cron set up to put the servers offline (rtcwake) while i'm sleeping, so that they wouldn't just go on droning in the background and to start up in the morning.
Since they do this every day with no exceptions, that's a decent amount of power cycling, in addition to them working all the time otherwise, which has been going on for about 5 years or so.
So essentially each of them has been on for about 30'000 - 35'000 hours and has power cycled around 1800 - 3600 times, because for the longest time i've had a cron restart set up right after the rtcwake sleep period finishes, due to some odd bug in the kernel that otherwise caused their CPUs to get stuck at 100% usage after waking up.
Over these 5 or so years, i've had:
All of the failures have happened around power cycling, never in the middle of otherwise normal operation.To my surprise, nothing has actually melted or caught fire, the last time when anything close to that happened was ages ago with my 9800 GT GPU which for some reason started getting really bad thermals (90 degrees C) and so i had to reflow solder it in the oven a few times, before eventually it just refused to work and artifacted out on boot. Or maybe i could mention a MOLEX connector stopping working, but i might just have a splitter in there due to not enough SATA connections from the PSU, something that people typically advise against.
So, to sum all of that up, yes, consumer hardware will definitely die from regular use under normal circumstances, probably moreso with regular power cycling of parts that aren't really made for that (especially the regular HDDs, which seemed to die right after restarts). Also, my case might be an outlier (and a sample size of 1), due to me not caring that much in university about keeping the servers in a good environment, but i bet that most consumer hardware has to deal with sub-optimal conditions in one way or another - accumulation of dust, bad airflow, air humidity, ambient temperature and power grid fluctuations all should also be taken into account.
I actually had to stagger the startup times for my servers, since otherwise they'd max out their power draw at the same time in the morning (e.g. when launching Docker containers and spinning up VMs), which also lead to some weirdness. Of course, the quality of the parts themselves probably also matters (like a reputable brand PSU vs the cheaper options that i could afford) as much as how they're used (prolonged periods of full load while everything starts up), as do other factors, like vibrations of the HDDs, for example.
Other hardware is similar.
But if I lost power to thousands of servers, I'd expect some number of them to fail. I've even lost servers when losing power to a single rack.