Water has a massive amount of thermal capacity and can quickly and in bulk be cooled to optimal temperatures. You'd probably still need fans and AC to dissipate heat of non-liquid cooled parts, but for the big energy items like CPUs and GPUs/compute engines, you could ship out huge amounts of heat fairly quickly and directly.
I guess the complexity and risk of a leak would be a problem, but for amazon sized data centers that doesn't seem like a major concern.
Liquid cooling is almost a defacto-standard in data centers in the HPC world. The Top of the TOP500 machines are all liquid cooled. Not by choice, but due to physics constraints.
There is a big gap in power density between the HPC world and the usual datacenter-commodity-hardware world.
Commodity DS are designed with the assumption that the average machine will run with a fraction of it's maximum load. HPC systems at the opposite are designed to operate safely at 100% load all the time.
In a previous company where I worked, we attempted to install a medium size HPC cluster in a well-known commerical datacenter and network provider. The commercial of the DS almost felt from his chair when we announced the power requirements.
Heh. We tried it too. They didn’t believe that a single node used their entire rack’s budget at first.
[1]https://www.supermicro.com/en/products/system/gpu/5u/sys-521...
Also, this involves a UK university where it would takes forever to upgrade the power delivery to the building/floor/room. There's no planned upgrade whatsoever so people just need to make do with what we have.
The one data point I know well is NERSC, and has been air cooled until relatively recently. Part of the success of air cool in the past was the great Bay Area weather that is typically cooled enough. I forgot the exact reason for upgrading to water cool, but it was before the recent upgrade to a new machine (Perlmutter). It may have to do with our weather getting more extreme so that there are more incidences that air cool only will “throttle” your machine.
The reason I’m skeptical about that claim is that the ambient temperature also play a role. But certainly the density is increasing so may be the biggest supercomputers at the moment are too dense (in power consumption) to be air cooled.
- Frontier: Liquid cooled
- Aurora: liquid cooled
- Eagle: liquid cooled
- Fugaku: liquid cooled
- Lumi: Liquid cooled with heat recycling.
The need for liquid cooled arrived with the usage of accelerators that bumped significantly the power density.
That said, Fugaku which is not accelerator driven is also liquid cooled today.
I am surprised to learn that NERSC was air cooled until recently. Most of the BGQ machines, that were dominating the top500 10 years ago, were already liquid cooled.
But perhaps you're right that the physics is the ultimate factor here: what comes in must goes out. With order of magnitude scale of increase in power coming in, water seems to be the most effective and cheap entity to absorb those heat and be transported outside the floor very efficiently.
You need two circuits, and a CDU between them. Coolants needs maintaining. You add antifreeze, biocides, etc.
Air is brute force. It cools everything it touches. Liquid cooling is serialized in a node. Two sockets? Second will be hotter. HBA not making good contact? It’ll overheat.
You add extensive leak detection subsystems, the amount of coolant moving in your primary circuit becomes massive.
Currently you can remove 97% of the heat via liquid (including the PSUs), and it’s cheaper to do so than air, but it’s not “rails, screws, cables, power on”. Air cooled systems can be turned on in a week. Liquid cooled ones take a month.
However, using liquid is mandatory after some point. You can’t cool systems that dense and under that load with air. They’ll melt.
But not convect. Hence why it’s much, much harder than removing heat on Earth.
Almost. It’s proportional [0] to T_hot^4 - T_cold^4. For a 100C surface with emissivity 1, that’s about 1kW/m2 if there is no radiation coming back, which really isn’t very high. You cannot cheat this with fancy folded-up radiating surfaces (it’s thermodynamically impossible, and the actual mechanism that kills it is one fin of the heatsink radiating right at the next one).
So cooling in space is hard. You’re not getting GPU-like power densities without a physically immense radiating surface extending way past those GPUs.
[0] Caveat: emissivity can depend on wavelength, and the law holds independently at each wavelength. So this can introduce interesting effects, which is how all the fancy prototype roof-cooling materials work, and it’s also related to how “spectrally selective” windows and window films work.
I've seen tests done on heavy PC loops (ie multi-GPU) both high-flow and low-flow, as well as on car engines, in different coolant flow configurations. The results from all of those are that the water doesn't rise meaningfully in temperature between components.
Unless I did my back-of-the-napkin math wrong, this seems reasonable. If you have a single 10mm ID pipe going through a 1U server and up to the next, then for a full 42U rack you have about 1.7kg of water going through the servers. If the flow rate is about 1s per server (so 42 seconds for the full rack) and each 1U server dumps 500W of energy into the water, there should be just a 3 degree C difference in the water temperature between the first and the last server.
> Delta T between two sockets is 5 degrees C
And secondly, ~5-10 degrees is what I see on my dual-socket workstation, and have been wondering about this delta ever since the first day I started monitoring the temperatures. At first, I thought that the heat sink wasn't installed properly but after reinstalling it the delta remained. Since I didn't notice any CPU throttling or whatsoever I figured it's "normal" and ignored it.
I mean, water travels from one socket to another, so one processor adds heat equal to 5 degrees C under nominal load. The second socket doesn’t complain much, but this is enormous amounts of heat transferred in a such quick pace.
I guess it could be bad past some %, but there's a probably a point where it's worth it.
https://blog.ovhcloud.com/water-cooling-from-innovation-to-d...
https://blog.ovhcloud.com/water-cooling-from-innovation-to-d...
https://blog.ovhcloud.com/new-hybrid-immersion-liquid-coolin...
[0]: https://www.opencompute.org/projects/cooling-environments
[1]: https://gitlab.com/open19/v2-specification/-/blob/main/syste...
Problem is that’s how you sell 1-3 racks not an entire room of them.
Ethylene lines might be more practical, easier to wire into existing systems.
I used to work in AWS, but on the software / services side of things. But now and then, we would crash some talks from the datacenter folks.
One key relevation for me was that increasing compute power in DCs is primarily a thermodynamics problem than actual computing. The nodes have become so dense that shipping power in and shipping heat out, with all kinds of redundancies is an extremely hard problem. And it's not like you can perform a software update if you've discovered some inefficiencies.
This was ~10 years ago, so probably some things have changed.
What blows me away is that Amazon, starting out as an internet bookstore is at the cutting edge of solving thermodynamics problems.