additional point, you wrote that you have current system installed 15 years ago. back than design temperatures (i.e. how hvac sized based on outdoor temperature) were different. recent updates sometime bring those temperatures up by 10F or so, what can result in extra half a ton - ton of hvac.
you could retain company to make a proper hvac sizing (called manual j calculation). hvac contracts from my expirience won't do it.
During summer, the night temperature drops to the low 90’s here. It’s A/C all day, every day, for at least 3 months.
Any idea why the HVAC guy and just about every source online insists that A/C can only give you a temperature delta of 20F? I know it can’t be true, but that claim is everywhere.
The delta-T that is correctly cited as being "around a max of 20°F" is the delta in temperature across the evaporator (IOW between the return duct and the supply duct). It's not the delta-T between the outside air and inside air.
With good enough insulation and/or enough cooling, you can get whatever delta-T you want as is obviously the case with refrigerators and freezers.
well said. i have temp sensor on supply and return and I graph them and delta, to make sure that hvac works within proper parameters. otherwise during heat waves you start thinking that hvac maybe out of shape
One more question- what about commercial spaces where they will have a door open and be flooding the store with ice cold air. It sure feels like more than a 20 degree difference.
That has (essentially) nothing to with the relationship between the indoor and outdoor temp.
For simplicity, imagine a balmy 110°F outside temp, an 80°F inside temp. That's 30°F from inside to outside [and will feel refreshing], but probably results from a supply temp [the coldest air coming right out of the vent] at 68°F, a return temp [the air being drawn into the AC duct] of 88°F.
The key 20°F delta-T is the measure between the 88°F and the 68°F (both temperatures inside the conditioned [in other words, "indoor"] space). All of the other temperatures can be all over the place. Even if the outside temp was 120°F, provided the unit was sized large enough or the insulation good enough, the indoor air might average 80°F and keep the same 88°F/68°F [20°F delta-T].
As a more extreme example, your freezer probably works on a delta-T of ~10°F. That's the difference between the air going into the evap coil area and the outlet. If your indoor kitchen temperature is 80°F, your freezer still keeps things frozen even though its delta-T is only 10°F. You don't take the 10°F from the 80°F. You take the 10° from the 30-ish°F and get a warm temp of 30°F and a cold temp of 20°F in the freezer.
are you sure ? at summer I have walls that are 170F outside (at 2pm) and 80-90F inside. Also, window will pass through heat only during the day. Wall will keep heating your inside air through the night as well. Get some cheap thermal camera - it's very educational.
You should also check your ductwork/registers. To see if there are any tears/openings/etc. Also, in case you are using flex duct, if it's not tensioned properly, sagging, etc - there will be a lot of air velocity losses that reduce overall cooling experience.
>Any idea why the HVAC guy and just about every source online insists that A/C can only give you a temperature delta of 20F? I know it can’t be true, but that claim is everywhere.
Something around refrigerant properties, mechanics and physics, etc. I also spent some time in this rabbit hole
They short cycle.
An over-sized system can quickly cool to the thermostat setting, but leave the latent heat in the water vapor in the air.
So you experience the "feels like" temperature...it's not the heat, as they say.
A properly sized system runs long enough to condense water vapor and with it remove the latent heat from the air.
A variable speed system integrated with a humidifier should be able to slowly bring the temperature down, making sure that the cooling does not get ahead of the dehumidifying.
I want an “oversized” system that can do > 20F temperature drops. I know they exist because a lot of commercial spaces have them.
In my case, I didn't end up with any super directly-actionable insights -- but it was still very well worth the money IMO. Even just to confirm that we weren't losing/"leaking" energy egregiously. The reality was, our household simply uses a lot of energy - hah.
I mention this all because, at the time, we were just about to replace our HVAC units & we had just installed solar + storage.
I'm located in Las Vegas -- summers are HOT (!) -- but our units (2x 5-ton Bosch heat pumps) can near-trivially keep us at 70F (or cooler), even on the hottest of days. I try to "push" the thermostats up a bit (we leverage a ToU energy plan), but there are days when the battle isn't worth having & the wife needs it at 69F -- and, even on the hottest Vegas days, we're able to hit it (can be expensive to do so, depending on time of day -- but is totally doable).
Edit to add -- Oversizing a system can very easily lead to issues; short-cycling, humidity control, etc. The ideal system will run nearly non-stop on "design" temperature days. See if you can find any highly-rated Bosch installers locally; they'd likely be willing to "oversize" a system since the Bosch units are "variable capacity" (inverter-driven), which means you're less susceptible to hitting some of the common issues/concerns when oversizing traditional systems. Alternatively, the high-end variable-speed options from major brands are generally well-regarded though they can be extremely expensive (the price segmentation, and resultant value propositions, are bordering on dubious IMO).
Our system is old enough that it’s just time to replace. It’s the one the builder installed 14 or 15 years ago and it’s fairly low end.
What you’ve accomplished in your home is exactly what my installer tells me they can’t do. He told me no matter how large of a system I buy, the system will never be able to pul the indoor temperature down more than about 20F (internet searches for “max ac cooling” seem to back that up). He says a bigger system will get me down to the 20F floor faster, but that’s it.
I don’t believe it though because of stories like yours and because commercial spaces around here are very cold on hot days.
If you have 2+ floors, you probably need (or have) zones, and it may be worth paying a professional to engineer a solution that meet your requirements. I recall finding some small businesses online that do exactly this for a nominal fee (<$500 IIRC).
You might also consider looking for residential HVAC companies that also do commercial refrigeration; the conceptual physics for commercial refrigeration aren't much different from residential HVAC, just specialized refrigerants & components that are tailored to those use-cases (ie labs often require extra-cold freezers, etc).
FWIW, my gut is you'd be happy with most variable-speed offerings, if sized appropriately. Low humidity here makes it easier, but I'm sure you can do what you want, but it may not be cheap.
I’ve talked to a couple of HVAC companies already because I want more cooling power. When it’s above 100F (which it is for 3+ months of the year) my current system struggles to hold 80F. If we use the oven on a hot day, we may not get the temperature back down for days. Our winters are relatively mild (we don’t get much below 25F). We’re in central Texas.
The HVAC companies I’ve spoken to won’t sell me an oversized system. They’ve never really said why, but from my research I think it has to do with mold problems resulting from cooling air with too much moisture in it. It doesn’t seem like a big ask for the thermostat to include humidity in its decision on how hard to run the AC, but apparently that doesn’t exist.
Would one of your systems solve any of these problems? I’m not a DIY person, so I don’t really want to buy direct. Do you have installation partners in the Austin, TX area?