well said. i have temp sensor on supply and return and I graph them and delta, to make sure that hvac works within proper parameters. otherwise during heat waves you start thinking that hvac maybe out of shape
One more question- what about commercial spaces where they will have a door open and be flooding the store with ice cold air. It sure feels like more than a 20 degree difference.
That has (essentially) nothing to with the relationship between the indoor and outdoor temp.
For simplicity, imagine a balmy 110°F outside temp, an 80°F inside temp. That's 30°F from inside to outside [and will feel refreshing], but probably results from a supply temp [the coldest air coming right out of the vent] at 68°F, a return temp [the air being drawn into the AC duct] of 88°F.
The key 20°F delta-T is the measure between the 88°F and the 68°F (both temperatures inside the conditioned [in other words, "indoor"] space). All of the other temperatures can be all over the place. Even if the outside temp was 120°F, provided the unit was sized large enough or the insulation good enough, the indoor air might average 80°F and keep the same 88°F/68°F [20°F delta-T].
As a more extreme example, your freezer probably works on a delta-T of ~10°F. That's the difference between the air going into the evap coil area and the outlet. If your indoor kitchen temperature is 80°F, your freezer still keeps things frozen even though its delta-T is only 10°F. You don't take the 10°F from the 80°F. You take the 10° from the 30-ish°F and get a warm temp of 30°F and a cold temp of 20°F in the freezer.
The delta-T that is correctly cited as being "around a max of 20°F" is the delta in temperature across the evaporator (IOW between the return duct and the supply duct). It's not the delta-T between the outside air and inside air.
With good enough insulation and/or enough cooling, you can get whatever delta-T you want as is obviously the case with refrigerators and freezers.