Re:Microsoft blames monster email outage on software defect ... by hwillis on Monday November 16, 2026 @07:53PM (#50525935)
> and can't keep frequency in the right range, which can damage equipment.

This is one of those beautiful engineer understatements. Rotational speed is fundamentally linked to voltage by the motor velocity constant: https://en.wikipedia.org/wiki/Motor_constants

Although it's fundamental for all motors, the actual constant is arbitrary for each motor. Voltage is still proportional to change in field is proportional to speed; at zero voltage you have zero speed.

A large dead AC load has its own speed- zero. It's connecting the engine without a clutch, but the engine makes hundreds of megawatts. The 6' wide generator wants to go from 3600 RPM to a standstill in a few inches. A full speed rotor can have up to 5 gigajoules of rotational inertia; over a ton of TNT.

On a live grid you've got a synchronoscope: https://youtu.be/LVozbX9Mn1c?si=RhRPIkuTVxh4Wseq&t=181

Which is great, because connecting it backwards would cause a slow motion explosion. On a dead grid the only thing saving you is the resistance in the wires; it would be LOUD if you connected to it and you would very likely increase the ventilation through the walls of the plant.

Re:Microsoft blames monster email outage on software defect ... by jeffreygoesto on Tuesday November 17, 2026 @02:44AM (#50528603)
Somebody sent on HN a while ago how a small water power plant is synced to the net [0], I found it super fascinating.

[0] https://youtu.be/xGQxSJmadm0?si=fVdJXtN0bCBX_fyW

Re:Microsoft blames monster email outage on software defect ... by cowlevel on Tuesday November 17, 2026 @04:13AM (#50529178)
That's for a different type of motor. Synchronous motors always run at line frequency no matter the voltage; induction motors always run at a bit less than line frequency. And stepper motors run at the step rate, of course they're not directly connected to the grid because that wouldn't work, but they are also voltage-independent motors.
Re:Microsoft blames monster email outage on software defect ... by arghwhat on Tuesday November 17, 2026 @12:40PM (#50535118)
nit: all motors follow their fields, and no motor is implicitly tied to mains grid frequency.

That we often bypass local field control and tie large industrial synchronous and asynchronous (induction) motors directly to grid is narrow and quirky special case that is common for historic raisins but really quite awful, with staged delta-star or dahlander winding relay tricks to go from insane start currents down to just absurd.

Brushed motors are just synchronous motors with a primitive mechanical field control attached, allowing them to reduce the field rate in response to load.

Re:Microsoft blames monster email outage on software defect ... by account42 on Wednesday November 18, 2026 @07:02AM (#50545256)
> historic raisins

How long do you need to dry a grape for it to not only become a raisin but a historic one?

Re:Microsoft blames monster email outage on software defect ... by AlfredBarnes on Tuesday November 17, 2026 @08:24AM (#50531033)
ima use this "increase the ventilation through the walls" for when people put holes in things. It's great.
Re:Microsoft blames monster email outage on software defect ... by QuantumNomad_ on Tuesday November 17, 2026 @11:10AM (#50533483)
It’s definitely up there somewhere near to “unscheduled rapid disassembly”.
Re:Microsoft blames monster email outage on software defect ... by trollbridge on Tuesday November 17, 2026 @08:45AM (#50531300)
Note that going to solar and power storage fixes a lot of this since it has far more control over synthesising the frequencies needed, as opposed to big spinning turbines with lots of inertia.
Re:Microsoft blames monster email outage on software defect ... by lowkeyoptimist on Tuesday November 17, 2026 @10:01AM (#50532300)
The Iberian Peninsula blackout last year would like a word...
Re:Microsoft blames monster email outage on software defect ... by bdamm on Tuesday November 17, 2026 @12:41PM (#50535139)
Ah, no. Solar and wind are great energy sources, but electronically synthesized sine waves (what you get out of a solar inverter) can also have feedback harmonics that can build into destructive frequency waves. It's not a huge problem as long as the majority of generation is backed by rotating mass, but increasingly power islands and ever more distributed solar generation is tipping the scale of that equation, so we're likely to see more of these sorts of distribution and transmission issues caused by poorly behaving frequency generators' emergent behavior.
Re:Microsoft blames monster email outage on software defect ... by aforwardslash on Tuesday November 17, 2026 @12:54PM (#50535352)
Actually, its the opposite; afaik, injecting sythesized ac requires an already running ac system so it can match the frequency. Its non-linear characteristics can cause catastrophic imbalances in the grid - see portugal/spain blackout.
Re:Microsoft blames monster email outage on software defect ... by eldaisfish on Tuesday November 17, 2026 @10:29AM (#50532717)
this is mostly irrelevant to synchronous generators and operating the power grid.

In a synchronised power grid, machine speed is connected to electrical frequency, that's it.

Voltage and reactive power are controlled by the strength of the rotating field, not speed.