Re:Slow Electricity: The Return of DC Power? (2016) by willis936 on Monday January 01, 2024 @09:46AM (#38832124)
Switching losses are less than ohmic losses. A few chips cost less than a lot of copper. The crossover point depends on the cable lengths, cable size, load, and voltage in question.

Let's do a quick example. 16 AWG carrying 12V. 16 AWG is 4 mOhm/ft. Let's say you have a 1200 W load (100 A, 0.12 ohm). Ohmic losses per foot of cable are 3%. So if you have a 15 foot cable it will use as much power as the load.

Edit: I think I responded to the wrong comment.

Re:Slow Electricity: The Return of DC Power? (2016) by amelius on Monday January 01, 2024 @04:20PM (#38835459)
100 amps through 16AWG? Man that's pushing it.
Re:Slow Electricity: The Return of DC Power? (2016) by nine_k on Monday January 01, 2024 @08:20PM (#38837021)
Absolutely. But with the voltage 10x as high, the current goes down 10x, too, and the power loss goes down, too, while the power stays the same. That's how things run on AC normally.
Re:Slow Electricity: The Return of DC Power? (2016) by Dylan16807 on Monday January 01, 2024 @05:04PM (#38835749)
Especially for a 15 foot cable. I'd expect a cable >10x the thickness with <1/10th the resistance.