Re:1000W 12V –> 220V Inverter by samtho on Wednesday May 31, 2023 @07:19PM (#36145787)
I use 48v for all my high power DC applications and I usually spin PCBs. Part of the reason I use 48vdc is that there are bunch of ICs and reference designs for PoE applications that run at this voltage level.

12v is a miserable voltage to work with in general: too high for most logic circuits and for LDOs to work effectively but it’s too low for any large load with high-power applications become cost prohibitive quickly due to the cost of the conductors. Fun fact: Auto makers have gotten away with under sizing starter conductors, despite it drawing 80-100A, because it is only energized briefly and the length of the run is very short.

Re:1000W 12V –> 220V Inverter by Animats on Wednesday May 31, 2023 @07:28PM (#36145862)
Much industrial automation runs on 24VDC. High enough that the losses within a cabinet are tolerable, low enough that there's no electrocution hazard.
Re:1000W 12V –> 220V Inverter by amelius on Thursday June 01, 2023 @06:04AM (#36149217)
If you keep your hands dry or if you're a male, then 48VDC can be quite safe too.

https://www.allaboutcircuits.com/textbook/direct-current/chp...

We're running out of copper. So better keep your voltages on the high end (but still safe of course).

https://www.cnbc.com/2023/02/07/there-isnt-enough-copper-in-...

Re:1000W 12V –> 220V Inverter by mbreese on Thursday June 01, 2023 @06:29AM (#36149366)
To save someone else looking for the answer to why being male is a factor here… (which I didn’t know about!)

> Oh, and in case you’re wondering, I have no idea why women tend to be more susceptible to electric currents than men!

The pain thresholds are given in a table that is split by men and women. I believe the assumption is different conductivity between “typical” male/female bodies, but it’s really not spelled out.

Re:1000W 12V –> 220V Inverter by amelius on Thursday June 01, 2023 @08:21AM (#36150131)
Yes, on one hand it's strange because body fat decreases conductivity, and women have typically larger amount of body fat (25% versus 15%).

https://www.ncbi.nlm.nih.gov/books/NBK218162/

However, men are typically larger, so perhaps that's the reason.

Re:1000W 12V –> 220V Inverter by ilyt on Thursday June 01, 2023 @11:49AM (#36152856)
Soo fat people are more shock-resistant too ?
Re:1000W 12V –> 220V Inverter by gaudat on Wednesday May 31, 2023 @08:01PM (#36146122)
And I think 48VDC is the highest convenient voltage you get before exceeding ELV. There are a lot of surplus telecom and server power supplies that gives 48V at decent current. Above that there is a real risk of electrical injury, at least according to regulations.
Re:1000W 12V –> 220V Inverter by samtho on Thursday June 01, 2023 @12:20AM (#36147531)
You can actually go up to 120VDC (with no ripple) before you’re out of ELV - which I always find surprising. You’re probably thinking of the A/C limit which is 50V RMS.
Re:1000W 12V –> 220V Inverter by gaudat on Thursday June 01, 2023 @12:31AM (#36147586)
Interesting, I thought the limit is at 60VDC.
Re:1000W 12V –> 220V Inverter by omegabravo on Thursday June 01, 2023 @02:15AM (#36148063)
IEC limits are 120VDC, 50VAC which quite a few countries will use (eu*/au/nz).

US NEMA/NEC is a very different standard.

Re:1000W 12V –> 220V Inverter by auxym on Thursday June 01, 2023 @07:43AM (#36149860)
60 VDC / 30 VAC in Canada per CSA Z462 (workplace electrical safety).