...wait, that's not helping?
That is, along with measuring temperature, the sensors in each room should also measure CO2 levels. If CO2 is rising, fans can be turned on/turned up to bring more fresh air into the room.
> CO2 monitoring equipment should be provided in the apartment expected to be the main or principal bedroom in a dwelling where infiltrating air rates are less than 15m3/hr/m2 @ 50 Pa.
https://www.gov.scot/publications/building-standards-2017-do...
Well done, Scotland.
If the law requires just monitoring equipment, then you know that in a utility cabinet somewhere will be a screen with the data on, that nobody ever looks at, and might as well not be there.
In fancier homes they can control the ventilation per room, though the standard is that they control the ventilation for the entire house.
As buildings approach airtightness, this becomes essential. I was expecting more in this area from the IoT crowd, but they never delivered. It's the old-school HVAC systems which do this.
Some years back I went to an IoT meeting in San Francisco, in a beautifully converted industrial building in Dogpatch on the waterfront. Big windows and skylights, with openable windows driven by manual chain falls on both. Ceiling fans. Plus a standard HVAC system. Was all of this coordinated in any way? No.
The place should have had motor drives on the windows. They were all on two long shafts, so it wouldn't be all that hard. As the place filled up with people, the skylights should be opened and the ceiling fans driven to blow upward and exhaust hot air and C02. Open the bay-facing windows slightly for intake air. As the evening went on and outside temperature dropped, close the bay-facing windows, continuing to monitor CO2 and temperature. If heating, open a damper to take air from the outside as necessary to keep the CO2 down. When everybody leaves, flush the air for a few minutes, then close everything up, turn off the fans, and let the temperature drop a few degrees.
The place should have been a showpiece for intelligent building control. But what were they pushing? Refrigerators with a tablet built into the door, for more than the cost of a refrigerator plus an iPad. The tablet had no useful interaction with the refrigerator; it was just a general use tablet.
Even home "smart thermostats" don't do much. They need this set of sensors, plus an external air damper so they can switch from recirculate to outside air as necessary. And the ability to run fans, without AC or heat as necessary. But that requires actual installation, which neither Amazon nor Apple can competently handle.
All this stuff saves enough energy to pay for itself.
[1] https://buildings.honeywell.com/gb/en/products/by-category/s...
Where does "opening the windows" fit in a scale of "well designed ventilation systems" ?
I'm not being flip, or snarky - I'm serious.
I don't think it's terribly sophisticated or haughty to consider lack of opening windows to be a poverty.
Hotel rooms, hospital rooms, classrooms ... whatever ... windows that cannot be opened is a poverty.
it's much more common to wish for bigger windows because you're hot than because you're falling asleep
(1000 ppmv - 420 ppmv) co₂ = 580 ppmv co₂
r 20° / 1 atm = 24 ℓ/mol
1 kg co₂ / day / 人 = 11.6 mg co₂ / s / 人
30 人 · 11.6 mg co₂ / s / 人 / (44 g co₂/mol co₂) = 7.9 mmol co₂ / s (a classroom)
7.9 mmol co₂ / s · 24 ℓ/mol = 0.19 ℓ co₂ / s
0.19 ℓ co₂ / s / 580 ppmv co₂ = 330 ℓ / s (of air)
in medieval units that's about 700 'cfm'
if the classroom has 10 m² of open windows you're fine, even an undetectable draft of 0.03 m/s is sufficient, but if it has 1 m² you need a barely detectable breeze of 0.3 m/s, if it has 0.1 m² you need a pretty noticeable breeze of 3 m/s ('light breeze' on the beaufort scale), and if it has a little 100-mm-square register you need 30 m/s which is a 'violent storm' on the beaufort scale (above 'whole gale')
at 'fresh breeze' (8–11 m/s) you need 300–400 cm² of window
well designed ventilation systems can provide this kind of airflow while controlling the temperature and humidity but they are at a big disadvantage because 300–400 cm² of window is a lot smaller than 300–400 cm² of duct
sometimes that's not what matters most tho
We had some employees complain about feeling "stuffy" when air conditioning was turned off(due to budget constraints).
So maintenance brought their own CO2 meter and I brought my trusty Aranet4.
Both our readings were around 650 in a medium sized office with 4 people. Apparently the raise of temperature from 22C to 26C was enough to trigger internal "stuffiness".
PS By comparison my bedroom regularly reaches 3000 in the mornings if no windows are left open.
The biggest differentiator is if the building has mechanical ventilation and to what extent this mechanical ventilation uses fresh air vs internal circulation.
In unventilated crowded spaces like e.g. classrooms, we regularly see CO2 exceeding 3500 ppm. [1]
However in classrooms with a well designed ventilation system you can keep the CO2 < 1000ppm during the whole school day.
What the author did in his hotel room to turn on the fan or play around with the A/C settings is a good idea but many hotels Hvac systems do not draw in sufficient fresh air and you will see high CO2 developments.
[1] https://www.airgradient.com/open-airgradient/blog/we-measure...