Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by walrus01 on Saturday February 24, 2018 @04:54AM (#16452547)
You can't run air conditioners directly off solar. PV panels natively produce DC. There are units with microinverters built into the back of the panel that produce AC. Even in a sunny climate clouds will pass in front of the sun. Unless you have a massively oversized PV array, you can't just run the DC array's output into a bank of sinewave inverters and then straight into the input of multiple 2 to 5kW load air conditioners.

I'm assuming here that a typical AC unit will look something like a 12000, 18000 or 24000 BTU/H LG, Daikin or Samsung split type, ductless, cooling-only unit.

The cumulative kWh/day and kWh/month produced by your PV is what you should care about. As compared to what your load will consume in the same time period.

For off grid, which now economically makes sense in much of Hawaii because fossil-fuel powered grid power can costs $0.32 to $0.50/kWh.

You need a battery buffer so that your load (the air conditioners) doesn't brown out and fail when the a few clouds pass in front of your PV panels. At a given time when it is a little bit cloudy out you might have 12kW of load but even a very big PV array might only be producing 4kW.

The load is constantly running off the battery and inverter system, while the PV panels and charge controller are constantly doing their best to keep the battery full.

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by Faaak on Saturday February 24, 2018 @07:18AM (#16452953)
Coming from Europe, I've never seen an AC unit expressed in BTU/hour. To me it seems much more logical to express it in kW.

The only "strange" (but correct) notation was on a french train, the AC was expressed in kcal/hour

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by y4mi on Saturday February 24, 2018 @08:53AM (#16453244)
Then you've probably never had to plan cooling for a server room. BTU's are often the only metric you get from the servers datasheet.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by walrus01 on Saturday February 24, 2018 @09:27AM (#16453343)
I find that these are occasionally very inaccurate. If possible put a prototypical server on a watt meter and artificially load cpu, disk and ram to determine its real world max wattage and thermal values. Then compare to what its wattage is while idle.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by altcognito on Saturday February 24, 2018 @09:50AM (#16453437)
At the scale of a server room, you're estimating over an aggregate and probably want some overhead/room to expand.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by walrus01 on Saturday February 24, 2018 @11:18AM (#16453879)
At the scale of a small to medium colocation facility you define W per cabinet... Such as a typical 44U height cabinet in a row designed for front to back airflow. 5kW per cabinet would be a normal low range, up to 10-12kW. Then figure out your floor spacing and sq ft usage to determine how many cabinets.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by make3 on Saturday February 24, 2018 @01:15PM (#16454485)
"Then you've probably never had to plan cooling for a server room."

For an American one you mean

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by y4mi on Saturday February 24, 2018 @02:07PM (#16454722)
i'm german, so no.

but i admit that its incredibly rare to find localized data sheets. they're generally en_us, not that it really matters.

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by mavhc on Saturday February 24, 2018 @02:12PM (#16454742)
Even British people don't use BTU
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by vidarh on Saturday February 24, 2018 @05:14PM (#16455749)
Every AC I've bought in the UK (5 so far) have been rated only in BTU.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by Animats on Saturday February 24, 2018 @01:40PM (#16454592)
1 watt = 3.412 BTU/hr.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by bringtheaction on Saturday February 24, 2018 @06:39AM (#16452853)
You used the word PV a lot but never said what it means. For anyone wondering, PV means photovoltaic.

https://en.wikipedia.org/wiki/Photovoltaics

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by walrus01 on Saturday February 24, 2018 @07:04AM (#16452921)
Yes, I forget that not everyone know the term. Work with solar on a regular basis and the whole industry is just as full of acronyms as x86-64 hardware.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by wernercd on Saturday February 24, 2018 @01:01PM (#16454416)
Any developed industry has it's own terms and language - healthcare, military, government, programming, finance...

Always fun learning new languages inside languages.

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by Someone1234 on Saturday February 24, 2018 @09:27AM (#16453344)
> You can't run air conditioners directly off solar. PV panels natively produce DC. There are units with microinverters built into the back of the panel that produce AC.

Why can't an air conditioner run off of DC? Just lack of availability?

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by SigmundA on Saturday February 24, 2018 @11:47AM (#16454048)
There are 48v DC air conditioners, again though you typically need a buffer with solar, either batteries or grid unless your way over paneled and even then you might get a cutout if a cloud goes over.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by JetSpiegel on Saturday February 24, 2018 @09:36AM (#16453378)
Can you run an electric motor on DC power?
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by andreyv on Saturday February 24, 2018 @09:46AM (#16453415)
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by geerlingguy on Saturday February 24, 2018 @10:04AM (#16453498)
I think he meant more ‘can you run an AC motor on DC power’ (benefit of the doubt), since almost all AC units sized for residential/business operate on AC power (to my knowledge?).
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by semi-extrinsic on Saturday February 24, 2018 @12:12PM (#16454168)
Modern ACs are powered by AC, but they run IGBT inverters to power a brushless DC motor. So you could build ACs to run on straight DC, but they would be a special application (so expensive initially).
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by namelost on Saturday February 24, 2018 @07:48AM (#16453039)
IANAEE but would it be possible to use a DC compressor and rectify the mains, instead of using an AC compressor and inverting the PV?
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by walrus01 on Saturday February 24, 2018 @08:40AM (#16453206)
You theoretically could, but then you would have a special weird setup that doesn't match 99.9% of the similar installation base of air conditioners on the same island. Making repairs, maintenance and such very costly. You generally want to generate usable AC power from any significant sort of solar system, so that you can use it for more than just air conditioners.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by sitharus on Saturday February 24, 2018 @08:01AM (#16453080)
Yes, but 3-phase AC motors require less maintenance and are more efficient than brushed DC motors. Most traction applications are now using AC motors with inverters instead of DC.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by lostapathy on Saturday February 24, 2018 @09:52AM (#16453450)
Powerwalls only output single phase AC, not 3-phase.

Brushless DC motors actually have an awful lot in common with 3 phase motors, though, in terms of operating characteristics and performance.

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by rdlecler1 on Saturday February 24, 2018 @06:57AM (#16452904)
I’d also assume that you get weekends to fully charge to give you a reserve buffer.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by sgc on Saturday February 24, 2018 @10:17AM (#16453554)
It's implicitly in your post, but basically a battery is a lot cheaper than a ton of extra solar panels since you can use your full day of solar during the peak period.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by amelius on Saturday February 24, 2018 @08:04AM (#16453086)
I think we need smarter ACs, not more batteries. A smarter AC would just continue to run with reduced output when there is less available power.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by zaroth on Saturday February 24, 2018 @11:15AM (#16453864)
Modern mini-split heat pumps are inverter driven and can step up/down their power consumption and cooling capacity pretty much in 1% steps — at least that’s what the marketing material claims.

Normally the cooling output is a function of the set point temperature vs current ambient and the fan speed.

So I’m not sure what you would need to add to allow the units to operate/respond to variation in available power from the panels but certainly they are able to operate at variable output levels.

Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by dmoy on Saturday February 24, 2018 @09:57AM (#16453466)
Is that not exactly what a brownout would cause, as GP alluded to? (I don't know the effect of low voltage on A/C so I'm guessing here...)
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to... by amelius on Saturday February 24, 2018 @10:20AM (#16453570)
I don't think a brownout would cause the desired effect (GP said "brownout and fail"). But what you could do is automatically switch off a selected set of A/C units when power output is low. That way you can prevent a brownout (drop in voltage), while still having some cooling. Of course, the A/C units should be designed such that frequent shut-offs are not a problem.

Anyway, I'm no expert either but I think the approach should consider the whole system (PV + A/C) rather than view them as different domains.