Then you've probably never had to plan cooling for a server room. BTU's are often the only metric you get from the servers datasheet.
[ Parent
| on HN ]
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to...
by walrus01 on Saturday February 24, 2018 @09:27AM
(#16453343)
I find that these are occasionally very inaccurate. If possible put a prototypical server on a watt meter and artificially load cpu, disk and ram to determine its real world max wattage and thermal values. Then compare to what its wattage is while idle.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to...
by altcognito on Saturday February 24, 2018 @09:50AM
(#16453437)
At the scale of a server room, you're estimating over an aggregate and probably want some overhead/room to expand.
Re:Tesla deployed over 300 Powerwalls in Hawaiian schools to...
by walrus01 on Saturday February 24, 2018 @11:18AM
(#16453879)
At the scale of a small to medium colocation facility you define W per cabinet... Such as a typical 44U height cabinet in a row designed for front to back airflow. 5kW per cabinet would be a normal low range, up to 10-12kW. Then figure out your floor spacing and sq ft usage to determine how many cabinets.