From what I've seen so far, unless your unit is super old, the 8.5A is almost certainly just a 'peak' startup current that's overstated as well. Your blower should say something like "1/3 HP" and from there it's straightforward conversion of 1HP = ~750W so a 1/3HP would be 250W. On a 120v service, that's 2 Amp. With maybe 15% efficiency loss, at peak speed, the blower motor wouldn't be drawing more than 2.5A. It could/will draw more than that to start, but literally just for a second or two.
https://d1049ui2fjityy.cloudfront.net/userfiles/inriver/docu...
That motor has a switch so it could be in 3 different settings -- As shipped, the blower motor speed is set to be faster for AC (more draw in the summer) to prevent the coils from icing over, and then it's shipped to be the slowest fan speed while in heating mode, but it is possible that your installer changed that. If indeed it is in the "slow" speed for heat, then 2.5A would be about right.
https://www.youtube.com/watch?v=1JNuovFpCpQ
* I don't like that they skipped putting a bushing or an NM clamp on the back of the box into the furnace, but otherwise the video looked sound when I watched it a couple weeks ago.