Re:Comcast's "fiber-powered Wi-Fi" is cable, AT&T says in fa... by throw0101c on Tuesday November 17, 2026 @11:21AM (#50533675)
> Reading that your AC alone draws 4 kW is wild to me.

That's often on start-up. I'm in an older Canadian house with 'only' a 100A service, and when the external AC unit kicks on there's often a flicker to lights.

It might not be a bad idea for me to install a soft start device (which would also probably help with unit longevity):

* https://www.microair.net/collections/easystart-soft-starters

You can find various before/after videos about them being installed and the drop in in-rush current.

Re:Comcast's "fiber-powered Wi-Fi" is cable, AT&T says in fa... by vel0city on Tuesday November 17, 2026 @12:20PM (#50534776)
Nah, ~16-18A @ 240V running for a 5-ton rated AC unit when its hot out were the measurements I took when servicing it this summer. The nameplate actually rates the unit for ~27 RLA (Rated Load Amps) with an LRA (Locked Rotor Amps) at about 140A. The unit is probably a bit oversized for my home.

Its usually pretty common to hit anywhere between 60-80% RLA during a normal summer day.

Re:Comcast's "fiber-powered Wi-Fi" is cable, AT&T says in fa... by cwillu on Tuesday November 17, 2026 @02:20PM (#50536741)
That sounds like a problem with a transformer in the neighbourhood; nothing about the 100A service implies that the voltage should drop enough to flicker lights when you get near that maximum load.
Re:Comcast's "fiber-powered Wi-Fi" is cable, AT&T says in fa... by throw0101c on Tuesday November 17, 2026 @03:28PM (#50537712)
> That sounds like a problem with a transformer in the neighbourhood

The house was built in the 1890s before electricity was even "invented": there are (disconnected) vestiges of knob-and-tube wiring, and gas lighting pipes before that.

Re:Comcast's "fiber-powered Wi-Fi" is cable, AT&T says in fa... by dfe on Friday November 20, 2026 @04:10AM (#50572091)
It's the neutral return of split phase that is the problem.

In a modern system the hot, neutral, and ground are all running in the same jacket (like Romex) or conduit. Topology is consistent for all wires in the system.

In a knob and tube system, each wire is individually wired inside the wall cavities. So it's often the case that a neutral wire might feed one set of outlets on one leg of the split, then go on to feed another set of outlets on another leg of the split whose hot wire runs a different route. In fact, that's kind of the whole point of K&T: keep the neutral and the hot away from each other as much as possible because insulation (at the time) was unreliable and shorted wires cause fires. And definitely keep the two hot legs even further away from each other if you can.

Even with perfect topology of a modern system, consider what happens when you are running a 10A appliance on one leg. 10A is flowing through the hot, and another 10A through the neutral.

Now what happens if we turn on 10A on the other leg of the split? 10A flows through hot A, 10 amps flows through hot B, and ZERO amps flow through the neutral because the loads are balanced.

If you turn on a device that has high reactance, like a vacuum cleaner motor has a lot of inrush current, then it can cause lights on the other 120V leg to get an unstable current while the electricity finds its way through the new load instead of the neutral, but then not so much current is needed after the inrush, so it has to find its way back to the neutral.

Now, imagine the neutral topology isn't consistent with the hot, as in K&T wiring. It exacerbates the problem.

Plus, no matter what you do let's say your maximum service ampacity is 200A and you have a balanced 240V load like a permanent A/C. The inrush current can cause the entire rest of the house to brown out for that moment as the incoming service simply cannot deliver that many amps without a significant voltage drop.

That said, it's the unbalanced 120V loads like refrigerators, portable A/Cs, and vacuum cleaners that really cause the flicker, especially in a K&T wired home.