> Wiring devices and breakers have accepted both Cu/Al wire for the last 50 years.

I agree with your general point, but be a bit careful here.

> Wiring devices and breakers have accepted both Cu/Al wire for the last 50 years.

It’s true that, for a little over 50 years, the UL has regulated what devices may “accept” Al wire. But devices have had markings suggesting use of Al wire for longer than that, and it was quite unwise:

https://inspectapedia.com/aluminum/Aluminum_Wiring_Repair_CO...

Don’t get caught up in all the discussion of repair devices — AIUI this article is mostly about “repair” of old pre-8000-series Al wire. You can’t buy that stuff any more. As far as I know, modern Al listed building wire is only sold in 8 AWG and up, and this stuff doesn’t need “repair”: it’s perfectly fine in any appropriately listed connector.

Re:What California Is Learning from Solar Panels Built over ... by quickthrowman on Wednesday September 23, 2026 @04:32PM (#49822132)
Ah I see what you’re referring to.

I was taught that the safe way to keep using the old pre-8000 series wire is to use the specific listed fittings for this purpose (WAGO 221 series nuts are fit for purpose) with contact paste and a copper pigtail that connects to the device.

Re:What California Is Learning from Solar Panels Built over ... by trollbridge on Wednesday September 23, 2026 @11:20PM (#49825829)
I assume you mean 222, and Wago's have earned a reputation for working themselves loose after enough years rather randomly to the point some reputable electrician outfits here won't use them. I would not bother with pre-8000 wire at all in thinner gauges (10 and thinner).