Re:Serving AI from the Basement – 192GB of VRAM Setup
by Dylan16807 on Sunday September 08, 2024 @06:21PM
(#41483729)
Do they actually install the 20A outlets with the sideways part? I don't know if I've ever seen one in person.
I guess the outlet doesn't matter a whole lot, especially if you take multiple cables to the wall.
But I still don't want to be doing unenforced electrical violations.
Re:Serving AI from the Basement – 192GB of VRAM Setup
by NavinF on Sunday September 08, 2024 @06:58PM
(#41483966)
Some outlets have the 20A sideways part, but from a safety/code perspective that's irrelevant.
Consider what happens when you plug two 10A devices into a power strip. In the US there are no true 15A rated outlets. All outlets must handle 20A because the electrical code allows any outlet to be on a 20A breaker.
Re:Serving AI from the Basement – 192GB of VRAM Setup
by Dylan16807 on Sunday September 08, 2024 @07:00PM
(#41483978)
> Consider what happens when you plug two 10A devices into a power strip.
I don't know about any argument that depends on such an action being safe. There's plenty of power strips I wouldn't trust with 20 amps.
Re:Serving AI from the Basement – 192GB of VRAM Setup
by NavinF on Sunday September 08, 2024 @07:10PM
(#41484032)
That's just how the US electrical code works. I assure you that every "15A" outlet on the wall can handle 20A. That's why products like this don't have a fuse: https://www.homedepot.com/p/Woods-2-ft-12-3-SJTW-Multi-Outle...
The NEC 80% rule is only relevant in data centers where someone enforces it. The time-current curve for any 20A breaker shows that it will take infinite time to trip when you draw 20A. This is correct behavior because 12awg wire can handle 20A indefinitely