Re:Battery-swap networks are preventing emergency blackouts by throwup238 on Tuesday June 11, 2024 @04:11PM (#40650925)
Yeah that's what the synchronization is for - the precise frequency doesn't matter except for consumer devices that use it as a clock signal. If the hot line is at 120V and you're a quarter cycle out of phase at 0V, all of that energy is just going to flow directly to your circuit and destroy something. Since the frequency represents the spinning of large turbines, a power plant going online out of phase is essentially slamming their turbines into a massive external force (things go boom).
Re:Battery-swap networks are preventing emergency blackouts by screcth on Tuesday June 11, 2024 @04:26PM (#40651069)
If you use GPS-based synchronization you have a reference of when zero crossings should occur. This does not mean that you have to output exactly that waveform.

Once you have a reference you can use a control algorithm. like a PID, to adjust the phase of the grid that you are generating locally.

If you sense that the grid is running out of phase from what your GPS clock says is the true reference you can increase/decrease your power output a bit to increase/decrease its frequency and catch up with the phase error.

It would be analogous to a type 2 PLL. The 1 Hz GPS clock would be the reference clock, the 60 Hz grid would be the "PLL output" and the VCO would be the power turbine, or AC inverter.

Re:Battery-swap networks are preventing emergency blackouts by burnished on Tuesday June 11, 2024 @05:03PM (#40651444)
Ok, potentially stupid question, but if you're already using the grid as a control signal what do you need the external clock for?
Re:Battery-swap networks are preventing emergency blackouts by screcth on Tuesday June 11, 2024 @05:23PM (#40651674)
From the comment I replied to:

> Generally grid backfeed capability for these systems is predicated on the presence of a stable voltage and frequency already on the grid.

You are using the reference clock to know precisely how misaligned the grid is and you use the reference to make small corrections to the generator power or inverter phase to restore phase alignment.

If you have an external stable reference clock (GPS) you know what the grid *phase* should be and it should be easier for network of multiple small inverters to keep the grid stable and to bring it up by themselves if there's a large blackout.

Re:Battery-swap networks are preventing emergency blackouts by burnished on Wednesday June 12, 2024 @07:43PM (#40664391)