If you've got 4 layers of 2oz copper, and you make the positive and negative traces 10mm wide, you'll only be dissipating 28 watts when the CPU is dissipating 300 watts. And most motherboards have more than 4 layers and have space for more than 10mm of power trace width. And there's a bunch of forced air cooling, due to that 300 watts of heat the CPU is producing.
Electrical code doesn't let buildings use cables that dissipate 28 watts for 2cm of distance because it would be extremely problematic if your 3m long EV charge cable dissipated 4200 watts.
This 350A is flat conductors (maximal surface area thus heat dissipation) and very short (not that much power to dissipate so the things it connects to have a significant effect on heat dissipation).
Processors operate at about 1V. At 300W it's enough to use a much smaller cross section, which is split across many traces.
On the other hand, your national electrical code is going to assume you're running that 350A cable at peak capacity 24/7, right next to other similarly-loaded cables, stuffed in an isolated wall, for very long runs - and it still has to remain at acceptable temperatures during a hot summer day.
Jesus. By German electrical code, you need a 70 mm² cross-section of copper to transfer that kind of current without the cable heating up to a point that it endangers the insulation. How do mainboard manufacturers supply that kind of current without resistive loss from the traces frying everything?