[1] https://en.wikipedia.org/wiki/High-voltage_direct_current#Ba...
Maybe imagine a line of buoys in the ocean as a wave passes.
(Perhaps the obvious answer is correct here: "Grids don't work that way; you'd never do that.")
Weird how all the replies so far misunderstood your question.
I'm pretty sure for home electronics the phase difference doesn't even matter that much. Everything sensitive seems to be converted to DC anyway.
Maybe it matters in large industrial applications, I have no idea. But I also imagine in their situation it's probably pretty straightforward to clean up the power supply.
In my imagination, the specialists are brought in only to learn that the RPMs in one motor were juiced because someone didn’t practice cable management
But... If you had a worldwide electricity grid running at 60Hz, it would start to matter, and you would make sure to use local capacitors/inductors to make phase shifts to make sure that you didn't have big circulating currents in loops (they just are wasting energy)
Imagine a triangle with 2 generators 100km apart, and a factory almost due south of one generator:
ga ......... gb
__f
I think the offset would be something like sin(gb.f) - sin(ga.f)
But really this comment is bait for an EE to school me.
Here's a video of old school mercury arc rectifiers as payment: https://www.youtube.com/watch?v=YhaQqgXrMMU
If you have local generation you want to combine with grid power you usually just sync your local generation to the grid. If you don't want to do that you can just use a DC intertie that is local. Basically you'd have two AC -> DC converters and a single DC -> AC converter.
The airport or hospital will procure transformers that have the same winding configuration and impedance so the phase shift and voltage drop across them will also be the same. The low voltage windings of the transformers at the hospital can be paralleled so they both feed the load. Reverse power protection would be implemented so the hospital can’t back feed the distribution line.
What phase difference do you expect in this case? What effect would it have?
You'd have to have 2 different routes from same power source that differed in hundreds of kilometers in length and that just doesn't really happen. And small phase difference would just cause uneven loading
Also that power would be "used up" closer to the power source and you'd be sucking off power from closer sources.
So the grid doesn't need to balance it, no.
And from the receiving end's perspective, power will be exactly one phase out of sync if the cables differ in length by 5000 km. I'm assuming that isn't really a problem people have to worry about, but my background is in physics and not engineering (i.e. maybe there's some industrial applications that I'm not thinking of).
Everyone isn't always in phase with every other station's phase at that exact moment in time. They're just in phase with their local part of the grid's phase. Though amount that is different is milliseconds, not seconds as in the stadium wave example.
This mostly came from reading this: https://electronics.stackexchange.com/a/291328
That’s described on https://en.wikipedia.org/wiki/Synchronization_(alternating_c....
Firstly, you design your generator to have the same wave form and phase sequence as the grid.
Then, you power up your generator and make sure the voltage, frequency and phase angle of the electricity it generates matches that of the grid.
The moment that’s (more or less) the case, you connect the grids, preferably on a zero crossing. That Wikipedia page describes a setup with incandescent bulbs that can be used to manually detect that moment, but nowadays, it’s done using electronics.
not in phase as such, but in sync.
because you only have to match your 60hz(or 50hz) to what you receive locally, so long as the waveform is reasonably stable its not that much of an issue.
Because everything is effectively a bunch of elastically linked pendulums, you tend to reach equilibrium, so long as the load doesn't act too much as a dampener
If everything is in a line, you just sync to your local phase, but if you have wires in a triangle that's impossible, and they basically just ignore it, in practice it doesn't happen often enough to cause any problems.
As far as I know, in your example, one of the two circuits will be transmitting more power from the substations to point B than the other. There's a device called a phase-shifting transformer (https://en.wikipedia.org/wiki/Phase-shifting_transformer) which can be used to adjust the phase angle of the circuits, and that way, adjust how much of the power is carried by each circuit.
(The following sentence from that article probably goes to the core of the answer for your question: "For an alternating current transmission line, power flow through the line is proportional to the sine of the difference in the phase angle of the voltage between the transmitting end and the receiving end of the line.[1]")
So the entire grid is in phase, by which I mean every generator, load, &c is operating on the same AC pulse (handwave-handwave ignoring smaller loads, transformations, etc.). But that phase isn't instantaneous; it's near-light, and the grid is long enough for that to matter in places.
So every point in the grid can't be perfectly in phase with every other point, right? Because we have both lightspeed delays and loops, so even if point A is receiving power from two substations in-phase, point B (with different lengths of wire to those two substations) should be receiving it out-of-phase, right? How do we balance that in the grid?