Re:Yandex data center in Finland loses power due to contract...
by FartyMcFarter on Wednesday May 04, 2022 @06:53AM
(#31258785)
I think that's wrong. One liter of diesel contains about 10 kWh of energy [1], so you need 4000 liters at 100% efficiency to generate 40 MWh.
12k liters per hour for the datacenter sounds about right, after accounting for diesel engine efficiency.
[1] https://www.sustainabilityexchange.ac.uk/files/cambridge_reg...
Re:Yandex data center in Finland loses power due to contract...
by dredmorbius on Wednesday May 04, 2022 @07:23AM
(#31258992)
Ramrodification caught my missing tonsoil -> barrels conversion.
Re:Yandex data center in Finland loses power due to contract...
by m55au on Wednesday May 04, 2022 @06:21AM
(#31258579)
No need to complicate things with obscure units.
You have: 40 MW/30% / (10722.2 W*hr/L)
You want: L/hr
40 MW/30% / (10722.2 W*hr/L) = 12435.259 L/hr
Re:Yandex data center in Finland loses power due to contract...
by dredmorbius on Wednesday May 04, 2022 @07:22AM
(#31258981)
GNU Units has builtins for some standard energy equivalent units, specifically "tonoil" and "barreloil". "litreoil" doesn't seem to be included by default (though it can be added via a local configuration file).
literoil = 1 barreloil * liter/barrel
And the calculation gives me ...10.69 kWh/LThe barreloil value is for crude, diesel may have a slightly higher net energy density. But we're good to 3 sig figs.
I could have bypassed the tonoil step and calculated thermal energy in barreloil directly though saving another conversion.
Otherwise I'd have to remember energy density/L of diesel fuel.
I've added the definitions for litre, pound, and kg oil and can now run:
$ units --terse '40 MWh/30%' literoil
12470.969
The fun part though, at least for me, is showing how to do conversions with GNU units, and the equivalences which become apparent doing so.
Re:Yandex data center in Finland loses power due to contract...
by m55au on Wednesday May 04, 2022 @07:45AM
(#31259170)
I looked around a bit in "definitions.units" and there are actually energy densities in there for various fuel sources, including diesel.
You have: 1 diesel
You want: Wh/L
1 diesel = 10103.465 Wh/L
Slightly different value than in Wikipedia, but close enough.
Re:Yandex data center in Finland loses power due to contract...
by dredmorbius on Wednesday May 04, 2022 @09:47AM
(#31260336)
*blink*
TIL, there are!
Thanks.
(For the curious, the definitions file is ~7500 lines, there's a lot in there. GNU version. For those on MacOS, the stock BSD units offers far less.)
Re:Yandex data center in Finland loses power due to contract...
by RamRodification on Wednesday May 04, 2022 @06:03AM
(#31258490)
Aren't you missing x3.4393809 on those ~1100 litres?
Re:Yandex data center in Finland loses power due to contract...
by dredmorbius on Wednesday May 04, 2022 @07:02AM
(#31258833)
Bingo, that's the error, thanks.
Corrected:
You have: 40 MWh
You want: tonoil
* 3.4393809
/ 0.29075
You have: 3.439 tonoil
You want: barreloil
* 23.529405
/ 0.042500012
You have: 23.529 barrel
You want: liter
* 3740.8121
/ 0.00026732164
You have: 3740/30%
You want:
Definition: 12466.667
Or a bit above 12,000 litres. Article was correct.
The generator is likely ~30% efficient at converting heat to eletricity, so bump that up to 3,700 litres/hour.
Even allowing for other inefficiencies, 12,000 litre/hr seems high to me. Though as a practical measure it may be correct. It's within a factor of 4 of the actual demand though.
(Calculations using GNU units.)