Re:Building a modern home in the woods by ReleaseCandidat on Thursday February 03, 2022 @12:13PM (#30195225)
> Am I the only one who almost spit out his coffee when reading this paragraph?

No, I thought that was a typo and should be 40A (so 120V * 40 A or 400V * 12A).

Re:Building a modern home in the woods by desdiv on Thursday February 03, 2022 @12:26PM (#30195458)
It's not a typo because 400A is indeed the highest tier residential service BC Hydro currently offers[0]. 400A is also in the right ballpark for the amount of equipment he describes.

[0] https://app.bchydro.com/accounts-billing/electrical-connecti...

Re:Building a modern home in the woods by rhacker on Thursday February 03, 2022 @12:41PM (#30195710)
The copper coming from "something" will be at least 1/2 inch thick, probably more so that it doesn't lose voltage. We're probably talking a 7/0 cable where 4/0 would be bare minimum.
Re:Building a modern home in the woods by pinot on Thursday February 03, 2022 @01:18PM (#30196334)
Probably larger than that. If they’re 200m from the transformer, 400A service requires (3) 1000kcmil cables per leg. 100m drops it to (3) 350kcmil which is still pretty beefy
Re:Building a modern home in the woods by ReleaseCandidat on Thursday February 03, 2022 @12:34PM (#30195604)
Oh, I believe that. The number is, well, unbelievable high, so I dismissed it as wrong without further thinking.