Re:Electronic meters’ false readings up to six times higher ...
by redrainbows on Sunday March 05, 2017 @02:21PM
(#13797926)
I'm interested in what area the overhead lines are only 1.1 kV. From what I have seen the high-side voltages are much higher, in the range of 7 kV or 14.4 kV line to ground.
Also, most overhead transformers I have seen are entirely single phase. Often you will see a bank of 3 single-phase transformers if a customer requires 3 phase service. Larger customers are connected to a pad-mounted 3-phase transformer connected to the primary overhead service through an underground dip from the pole.
Re:Electronic meters’ false readings up to six times higher ...
by hydrogen18 on Sunday March 05, 2017 @03:24PM
(#13798356)
You can't "take in 3 phase and output single phase". That's not how a transformer works. It'd be amazing if it did, as in Nobel Prize winning.
In the US most homes are just tapped to 1 phase, if there are 3 on the pole.
Re:Electronic meters’ false readings up to six times higher ...
by gfisher on Sunday March 05, 2017 @04:27PM
(#13798782)
Yeah, you are right. I think what they were trying to say is that the transformers are fed on the high side by one of three phases (as is typical), and that the residential step-down is a split phase 120/240.
Re:Electronic meters’ false readings up to six times higher ...
by hydrogen18 on Monday March 06, 2017 @08:30AM
(#13802474)
Yes, that is the normal configuration for power delivery to a residence in most of North America.
Even in apartment buildings, each apartment has its own meter, almost always single phase.