Nukes aren't great for load following, but they can load follow some--which is better than wind and solar. To really load follow, you need hydro or nat gas turbines (though nat gas combined cycle can load follow).
What this comes down to is, when you ramp down a fission reactor, there's some internal inertia in its internal workings, that will actively prevent it for some time from being able to ramped up in a safely manner. The quicker the shutdown, the larger the amount of neutron poisoning and the longer you have to wait before ramping it up again. This leaves you with a nice second order differential equation coupling the power output modulation factor with the period of that power modulation.
The period of the power modulation is 24h, following the daily load swings, so for a given reactor that gives you only so much load following capacity to stay within safe margins.
[1] https://www.oecd-nea.org/nea-news/2011/29-2/nea-news-29-2-lo...
"Most of the currently operating Generation II nuclear reactors were designed to have strong manoeuvring capabilities. Nuclear power plants in France and Germany operate in load-following mode."
"The economic consequences of load-following are mainly related to the reduction of the load factor... In France, the impact of load-following on the average unit capacity factor is sometimes estimated at about 1.2%."
"Licensing of load-following is specific to each country. In France and in Germany, for instance,load-following is considered early in the licensing process, and no further authorisation needs to be obtained by the utility to operate in manoeuvring regime. In other countries, load-following restrictions apply: for example in the United States, automatic load-following is not authorised"