> How often do you see multi-drive failures(in the same lun)?
It happens - usually for a reason. Most recently a bunch of drives of one model all seemed to fail very closely together after running for 2 years, it's like some part wore out like clockwork. We are pretty relaxed about 1 drive popping, nobody gets out of bed and runs to the datacenter for that, it can wait until the next morning (the pods instantly and automatically put themselves in a state where customers can prepare restores but we stop writing NEW data to them to lighten the load on the RAID arrays). So if 2 drives fail within 24 hours on a Sunday then Monday morning we go fix it.
> each rebuild caused more drives to fail.
Same exact experience here, we feel your pain. We even have a procedure where we line up all brand new drives, clone each individual original drive to a new drive, then take all the new drives and insert them back into the original pod AND THEN run the RAID rebuild.
How often do you see multi-drive failures(in the same lun)?
We've just past a peak of drive failures (had a power outage) where we've had multi-drive fails in the same lun. The awesome part about that is that each rebuild caused more drive to fail. I think one array swallowed 5 disks in two weeks. It didn't help that the array was being hammered as well as rebuilding (70 hour rebuilds at one point)