> Requiring every device to have its own rectifier is a lot less efficient than putting a single good rectifier in a central location.

Is it, though?

You'd have to deal with additional wiring losses due to the lower voltage between the central rectifier and the devices, and the various individual devices would still need their own step-down converters to turn that 48VDC into something they can actually use.

On top of that: the central rectifier would have to be sized for peak load, while in reality the vast majority of the time it would be running at only a fraction of that. That's not exactly ideal for efficient operation. Individual power supplies can be designed specifically for a single device and operate at its sweet spot most of the time.

Re:The MacBook Pro's OLED PWM Problem: When a 'Better' Displ... by dreamcompiler on Sunday November 15, 2026 @05:26PM (#50511504)
> You'd have to deal with additional wiring losses due to the lower voltage between the central rectifier and the devices

No. Everybody always complains about voltage drop. It's not a problem with LED lighting loads because they use so much less power. Let me prove it to you.

Assume we use the same 14-gauge copper Romex for our 48VDC lighting circuit that is already inside most home walls in the USA.

DC resistance of 14-gauge copper wire: 0.002525 ohms per foot.

Voltage drop over a circuit:

  Current x Ohms/foot x Two-way distance
  --------------------------------------
               Nominal Voltage
Assume we're driving a 13-watt LED bulb (typical 100W incandescent equivalent) that is 50 feet from the supply.

Current would be 13w/48v = 270mA.

  .270A x 0.002525Ohms/foot x 100feet
  -----------------------------------
            48v

  = 0.00142V
So the voltage drop is 0.14%. Any voltage drop less than 3% is considered acceptable by NEC.

Oh, but what if I want to run more than one bulb? Fine, let's do 10 bulbs on the same 14-gauge supply wire. Now the voltage drop is 1.4%. Still less than half the maximum limit.

And this is 14-gauge wire. What about 12-gauge? Well, that's 0.001588 ohms/foot.

  .270 x 0.001588 x 100
  ---------------------
           48
Now for 10 bulbs the voltage drop is eight tenths of a percent.

Running LED room lighting in a standard American house at 48VDC on the 14-gauge wire that's already in the walls is completely doable.

Yes, we still need constant-current supplies in or near the bulbs, and those are not 100% efficient. Keep in mind also that some of that 13 watts we assumed above is for typical Home Depot 120VAC bulbs that have builtin rectifiers and [probably] crappy power supplies, so the waste power used by the constant-current supplies I'm talking about here -- which are simpler than the supplies used in Home Depot bulbs -- is probably less.