by bluGill on Friday March 27, 2026 @10:42PM
(#47551027)
Right, but the NEC spec arc fault as well (i've only seen this on breakers). recepticals are cheaper and otherwise just as good.
[ Parent
| on HN ]
Re:Suddenly energy independence feels practical:Europeans bu...
by conk on Friday March 27, 2026 @11:49PM
(#47551441)
Because NEC 210.12 requires all devices to be protected. Which means if you have a switch or splice before a plug the only way to protect those is with an AFCI breaker. The only exception is a continuous run from the breaker to an outlet in metal conduit or MC cable. Given how much is romex this effectively forces AFCI branch breakers.
Re:Suddenly energy independence feels practical:Europeans bu...
by sgc on Saturday March 28, 2026 @01:15AM
(#47551856)
I find that receptacles tend to break prematurely if they are wet locations, even if 'protected' with a weatherproof box etc. You also need to know where the receptacle is and make sure it is accessible instead of behind a piece of furniture etc. Then some electricians misunderstand and put receptacles throughout the run (much more expensive than one breaker which is about 2x a receptacle), and in edge cases you need to know the order in which to reset them to get things working again. I much prefer to just have everything in the panel.