I personally wouldn't worry about a grounding rod if I was just running a few extension cords from the generator to power a handful of necessary things. The important thing is for all of the devices to be grounded back to the generator. This means 3 conductor cords for 3 prong devices, 4 conductor cords for 4 prong stove/dryer. 2 conductor non-polarized cords should be fine for modern 2-prong "double insulated" devices. In NO circumstance do you want to be using a 3-prong to 2-prong "cheater" adapters or anything similar.
Once you start talking about transfer switches and wiring it into your house, the picture completely changes. Unless you have experience doing house wiring, are up for dealing with live non-current-protected wires, and are open to learning something new while meticulously checking yourself, you really do want to talk to an electrician
The instructions completely didn't say what to do with it. When I looked it up online people are saying you need to have an 8 ft metal rod going into the ground?? Who's going to do that for a portable generator.
What do you guys do for grounding? And if you install a transfer switch does that change the grounding needs?