Re:Replacing Wires Could Double How Much Electricity the US ... by necheffa on Wednesday April 10, 2024 @10:03PM (#39997703)
Assuming above ground lines:

On the same "holder", no, just due to how the wire is fastened to the poll. On the same poll, maybe, depends on how much poll real estate is available. Usually though there is not extra space available. High voltage conductors use the air gap as part of its insulation so to prevent arcing the conductors need to be spaced out so far apart.

Re:Replacing Wires Could Double How Much Electricity the US ... by persolb on Wednesday April 10, 2024 @10:27PM (#39997815)
Is the air gap actually an issue in this case? If I'm understanding correctly, the suggestion is to put up additional cable instead of thicker cable. The two ends of the cable are both still connected to the same electrical phase, so there should be no arcing between them.
Re:Replacing Wires Could Double How Much Electricity the US ... by doctorwho42 on Thursday April 11, 2024 @12:30AM (#39998385)
Let's assume just high voltage cables (110kV [110,000 volts]}, if you put two cables connected to the same source and terminus, over 100 miles of cable you will easily see resistance variation between the two... Not including any environmental changes. High voltage starts to become a bit of magic when it comes to shielding it. You could have an inch of rubber insulation around that cable, and still have a static charge build up on the outside. If another cable or ground path is within a certain distance, you are going to cause arcs depending on the RH% in the air. One arc will cause degradation to the point it arcs to, and if it's the other cable - that will improve it's ability to arc again.

Long story short, when you start to enter the kV range, your traditional rules of thumb go out the window. I have first hand experience with trying to keep a particle accelerator from arcing, and that was a nightmare ... I can't imagine mixing in high current as well.

Re:Replacing Wires Could Double How Much Electricity the US ... by 7952 on Thursday April 11, 2024 @02:41AM (#39999044)
HV powerlines often use bundles soacedd at around 40cm that are regularly linked with conducting fittings.