Re:Replacing Wires Could Double How Much Electricity the US ...
by GauntletWizard on Wednesday April 10, 2024 @10:01PM
(#39997697)
It's a combination of heavy and tense, but yes - Trasmission towers are typically overengineered for their load, but not so much that you can go adding additional conductor strands to them. Further, there's significant distance requirements between strands - otherwise you get arcing.
[ Parent
| on HN ]
Re:Replacing Wires Could Double How Much Electricity the US ...
by ars on Thursday April 11, 2024 @12:28AM
(#39998375)
The distance doesn't matter, the additional cable would be at the same voltage as the one adjacent to it.
Re:Replacing Wires Could Double How Much Electricity the US ...
by GerryB on Thursday April 11, 2024 @03:17AM
(#39999229)
The different lines are at the same AC voltage, but have different phases (almost always three phases), so there's an instantaneous potential difference between them. The lines need to keep the conductors seperated to prevent potential arcing chances to essentially zero even in wet weather. The higher the voltage, the more seperation is needed.
Re:Replacing Wires Could Double How Much Electricity the US ...
by ben_w on Thursday April 11, 2024 @03:37AM
(#39999358)
My mental image for this whole thread is a UK steel pylons with 7 sets of cable — 3 groups of 4 wires on the left, same on the right, and a lone cable on the top.
I assume that's 3 because 3 phase.
But the point is, each is a group of 4: https://en.wikipedia.org/wiki/Overhead_power_line#/media/Fil...
I think the question is: can towers holding single wires for each (phase?), support e.g. four like this?