Re:We need a lot more electricians if we’re going to electri... by newZWhoDis on Wednesday January 11, 2023 @11:29AM (#34340275)
Required to sheath ground in green? What on earth for? That makes ground less effective since you want any incidental contact with ground to ground the object touching it.
Re:We need a lot more electricians if we’re going to electri... by londons_explore on Wednesday January 11, 2023 @11:33AM (#34340341)
Electrical specs are very strict.

They aren't just about electrical safety directly, but also about not potentially confusing people in the future.

If the cable was black, then someone may not have known that it was an earth cable, and might have cut it, which would leave your electrical installation unsafe.

Thats the reasoning why using the wrong color for a wire can make it illegal.

Re:We need a lot more electricians if we’re going to electri... by vel0city on Wednesday January 11, 2023 @11:58AM (#34340819)
That's the thing though: the best choice for a ground wire is no color at all, just the raw copper wire.
Re:We need a lot more electricians if we’re going to electri... by BitwiseFool on Wednesday January 11, 2023 @11:35AM (#34340372)
The part of the wire that is connected to the grounding object has no sheathing, but the length of the cable is insulated. The old cable was the same way. The coating was black and looked identical to the other wires running through the wall. I assume the justification for the code is that it makes the ground wire visually distinct.
Re:We need a lot more electricians if we’re going to electri... by actionfromafar on Wednesday January 11, 2023 @11:30AM (#34340297)
It was probably sheathed in black or some other color originally.
Re:We need a lot more electricians if we’re going to electri... by micromacrofoot on Wednesday January 11, 2023 @11:39AM (#34340453)
Because without a common language for what color wires carry load a simple oversight can be fatal.
Re:We need a lot more electricians if we’re going to electri... by frosted-flakes on Wednesday January 11, 2023 @02:59PM (#34343763)
Except a bare wire is always a ground.
Re:We need a lot more electricians if we’re going to electri... by bluGill on Wednesday January 11, 2023 @11:50AM (#34340654)
I believe that either a bare wire or a green wire is allowed. However no other colors. That was the case ~6 years ago when I checked the NEC.
Re:We need a lot more electricians if we’re going to electri... by DannyBee on Wednesday January 11, 2023 @01:56PM (#34342803)
Bare is allowed depending.

It is only required to be "primarily green". So the common alternative of green with yellow stripe is also allowed.

You can reidentify black cable if it's large enough gauge (6 awg currently).

Re:We need a lot more electricians if we’re going to electri... by georgeoliver on Wednesday January 11, 2023 @02:15PM (#34343086)
I was a little surprised to read the original comment too. I've never seen a sheathed ground wire used in WA state (on residential).
Re:We need a lot more electricians if we’re going to electri... by sowbug on Wednesday January 11, 2023 @12:00PM (#34340843)
"What on earth for?"

rimshot

Re:We need a lot more electricians if we’re going to electri... by stjohnswarts on Wednesday January 11, 2023 @12:32PM (#34341339)
* * *
Re:We need a lot more electricians if we’re going to electri... by DannyBee on Wednesday January 11, 2023 @01:55PM (#34342783)
Bare ground is allowed in lots of cases. The requirement is that insulated ground wires must be primarily green (IE green with yellow stripe is okay), but this is actually not new.

They must be > 6 awg to pull black and use green tape on the ends.

See 250.119.

This has been the case for a very long time though, at least since 2007 NEC. I don't have handy copies around for before then.