However, we put in a gas combi-boiler for hot water. Since we were renovating a townhouse, it was easy to throw in some radiant heaters on all floors. It’s a quiet, comfortable heat. I have the heat pump set to assist if the temps drop below 68F inside. All that said, insulation and air sealing is by far the most important thing to do first.
FYI: I checked the specs on my unit. It claims a 3.3X COP. So that’s $3 per therm, same as gas.
Now a question to address is whether your radiant heat is actually getting 95% efficiency. If you have an old radiator design system that was converted to using a condensing boiler, it may not be designed to keep return temperatures low enough for the boiler to operate at maximal efficiency. (old boiler systems were designed to keep the return water supply hot to prevent acidic condensate from eating the heat exchanger. This is the exact opposite of what you want with a modern system, where the return water needs to be cold enough that the flu gases condense into it to recover heat.)
If you have a way to monitor the return water temperature into your boiler, you could check. You need the return water to be below about 100 Fahrenheit in order to have 95% efficiency.