> don't touch it" is much better advice
Saw one heat pump controller discussed which had a curve set for demand vs outside temperature, and the "thermostat" was to set a delta relative to this.
Not for heat pumps. In a typical configuration (large heat reservoirs combined with under-floor heating in a well-insulated house), temperature-setpoint changes take 12-24 hours to propagate.
So, governing the (in-room) target temperature settings is unreliable/unpredictable. Whereas the in-pump storage temperature is a whole lot more manageable.
The old advice "turn your thermostat down at night" therefore also doesn't apply to most heat pump installations -- in fact, it might be disadvantageous. "Select the average temperature you need and don't touch it" is much better advice. Need localized heat/cold? Use another solution for that...