can being the operative word - the LRA (Locked Rotor Amps) of a typical fridge/freezer's compressor might be that high, but starting current is not unless something is hideously wrong. I've never metered mine, but I have ran three fridges and a deep freezer off of a 2200/1800 (start/run) watt generator with zero issues, and plenty of headroom left. The generator has tiny dip when the compressor kicks on, and then it jumps back.
You are correct that sizing cords is very important, though, and something that most people don't do. Also if you have a roll-up extension cord (the kind with multiple outlets at the end), it's vital that it is completely unrolled when in use, so the cord doesn't heat itself.
I run 12 gauge splitters --> 14 gauge for individual loads, but I also know exactly how much those loads are pulling, and have verified it's within safe limits for the wiring.
It's worth remembering that a house's wiring is almost always 12 gauge, and is rated for 20 amps assuming the correct outlet.
I used 12 gauge in my house on purpose but sadly I don't think that's the norm.
Notably:
* Kitchens must have at least two separate 20 amp circuits (for use for small appliances on countertops, traditionally) for general use
* Fridges need a dedicated 20 amp circuit
* Microwaves need a dedicated 20 amp circuit
Beyond that, yeah, absolute minimum is 15 amp throughout the house.
The code does seem to get a bit better over time.
Folks, spring for one or two good 50+ ft extension cords. You don't need a lot of them and the cheap ones are bad for your equipment and your safety.
> wasn't just safer but also visibly more powerful
All that energy that used to go into heating up the extension cord, are now getting to your tool.I personally argued with the guy who installed my EV charging station, because I wanted thicker wire and was willing to pay for it. I don't want wires heating up, I don't care if it's code compliant it is energy wasted that could go into my EV. And the thicker wire is not much more expensive nor difficult to work with.
I can't help but face-palm at this sort of hand wringing. It might not be "right" but it works.
If the 16ga cords regularly melted people wouldn't buy them in those lengths, they wouldn't fly off the shelves, they'd get stocked in lower volume and you'd see less of them on the shelves.
The fact that they don't melt themselves even when used with fairly substantial appliances (large-ish homeowner sized table saws and compressors, all manner of portable power tools) is a testament to how conservative the official recommendations are.
>and was shocked to discover my lawnmower wasn't just safer but also visibly more powerful, which I didn't think was possible.
Voltage drop
I'll grant you a contractor's usage of any tool is much higher than a typical homeowner's, there's still no reason not to get the beefier cord. Buy once, cry once.
A quick note: It should cost more than $20. When fridge compressor cycles on, it can draw up to 20A. Extension cord wire gauges are based on 1) length and 2) amperage and depending on home layout, you'd might get away with a 50 foot 12 gauge cord ($40). If it's 100 feet, you'd want 10 gauge ($100+). It'll vary by cord and refrigerator, and there are many extension cord sizing guides freely available.