Re:Hacker increased chemical level at Oldsmar's city water s... by jcranmer on Tuesday February 09, 2021 @01:23AM (#26074489)
Your understanding is incorrect.

It depends on what contaminant you are measuring, but the testing frequency can vary from "every several years" to "continuously monitored and sets off a SCADA alarm if it exceeds a given threshold." The biggies--IIRC, turbidity, pH, and dosages of coagulant and treatment chemicals--are logged every 15 minutes, with more tests happening on hourly 6-hourly, and daily frequencies, followed by yet more contaminants happening largely on monthly or quarterly assessment bases. The issue in question would have shown up in a pH measurement, so there's no reason it shouldn't have been caught within minutes.