Re:That UPS you bought for your home server may not be as us...
by zaarn on Wednesday August 12, 2020 @02:42AM
(#24129192)
The cables have fairly high ratings but in the even of a short circuit, the ratings have a safety margin of about 10x that the cable can last about 6 hours under, above the normal rating under standard conditions (ie, not fire).
At to amperage ratings, don't you just mean that they have a 10x safety factor? Probably using current limiting supplies that can handle a short circuit. Fire circuits (and the feed from the main panel) should use fire rated cabling -- generally mineral insulated copper sheathed cables. Most of the standards (NFPA 75/76) are moving away from being prescriptive to being risk or performance based though, so it is possible they used normal conduit if the overall risk was small.
Incidentally, hospitals also make extensive use of isolation transformers for wet areas (like emergency / ICU), to provide a local point for resetting breakers (electronically), identifying which point is tripping, etc, see IEEE 602-2007. Much better filtering for medical equipment too. You also tend to see positive retention plugs (in the US, green dot UL 817).