Alternatively, if you can prove that a single ground rod has less than 25 ohms to earth, then a single rod suffices.
If I have time later, I’ll try to look up the actual reference, but I remember reading and thinking “that makes no engineering sense!” so it stuck in my head.
Its actually IEEE and NFPA that recommend a maximum of 5 Ohms for the grounding system.
NEC state less than 5 Ohms for sensitive equipment, 25 Ohms otherwise. (NEC 250.56) - but as you mentioned, the measurement is only taken from first rod and a second can be inserted without testing (so it could be over 25 Ohms still, but based on the code it doesnt even matter....)
As an aside, its 200 Ohm in the UK (but it HAS to be measured - cant just blindly drive 2 electrodes and call it a day).
There are a few other (safer) ways that might interest HN readers, so sharing this video: https://www.youtube.com/watch?v=Yg6G5VUSsWA
I love electricians (and electrical engineers).
I did the calculations. One rod would have done it. Two if you wanted redundancy. The plan checker wanted four. Want to know why? He wanted one next to each post. As simple as that.
They want $1000 for a permit which would increase my payback time by at least 3 years.
I closely follow the relevant codes that improve my children's safety, but about half of the codes in my county are more about bureaucracy then safety.
Not saying safety isn't important. Quite to the contrary. However, there's safety and then there's making life impossible with things that don't really add to or enhance safety.
I am not exactly following code, as my earth comprises a 5 meter RSJ left over from construction buried 30cm down under a dirt road - we have very little soil over bedrock, but the soil is full of iron. It’s only half buried but I’m at 2.2 Ohm, so it should do the job - have soldered a nice fat cable to it to be my common ground.
The code says MINIMUM of 8ft in contact with soil. MAXIMUM earth ground impedance of 5 Ohm. So you need to keep driving in rods (or use an alternate grounding system) until you are below 5 Ohm - hence your multiple rods.