normal fuses (in the fusebox) still have to be 16A (B or C class), the main fuse can be anything 32-50A or even tri-phase 50A.
>ring circuits up to 100m, cookers and electric showers up to 7200W
Normally those tend to be 3phases.
Of course it's possible to get over 16A on a single phase and a circuit breaker but that's quite a non-standard option. The issue is that if the fuse/circuit breaker is rated for 32A in a standard application (i.e. an outlet) the cables are likely to burn 1st.
Re:Pre-built solar homes could make renewable energy almost ...
by benj111 on Monday September 30, 2019 @11:44AM
(#21116582)
I think we might be getting our wires crossed :)
I'm talking about the UK here, which I understood to be similar to the rest of Europe(?).
That's a UK website and 3 phase isn't common here. I've just double checked my fuse box, and I have a 32 amp fuse for my socket ring main.
Don't forget for a ring main the current is spread over 2 wires, so if theres 32amps power draw, theres only 16amp on each side of the ring.
"Use a 30amp fuse or 32amp MCB for larger radial circuits, ring circuits up to 100m, cookers and electric showers up to 7200W"
http://simplifydiy.com/electrical/basic-electrics/fuses