The entire purpose of the EGC is to bond all normally non-current carrying conductive parts together to provide a ground-fault current path back to the source of the circuit. If the EGC is not connected to some non-current carrying conductive part, then it is not installed correctly, is against code, and is a safety hazard. If the EGC is bonded to everything properly and there is a fault (say an ungrounded wire touches a metal box), then the current will flow through the ungrounded conductor, through the metal box, through the EGC (which is bonded to the box), back to the source (usually a transformer), across the windings, and eventually back to the breaker that controls the circuit. This will build up enough current (usually VERY fast, like milliseconds) and the breaker will open. The Earth has nothing to do with this.
Also the EGC does have more purposes than simply clearing fault current - for example carrying away leakage current from the chassis of something with a switching power supply where the output can't be completely isolated to meet emissions. Ever been shocked by a laptop with only a two-prong AC adapter?
IMO this whole subject is a minefield of disagreements due to terminology, when really all questions are answered by drawing out the schematic of a typical electrical system and looking at the loops (circuits). For instance in the typical ground fault, the fault current returns to the distribution transformer in parallel through all of: your service's neutral, your grounding rod, your neighbors grounding rods/service neutrals, and your other leg of the split phase via turned-on devices. This seems like a lot of unrelated details to memorize until one draws it out.
EGC is bonded to the panel enclosure at the ground bus. The neutral bus is also bonded to the enclosure with a ground screw. So, the EGC is directly connected to the neutral bus and a fault between hot and a bonded enclosure is routed via the EGC to neutral, tripping the breaker.
If you don't bond neutral and ground at the main, it's still bound at the transformer.
> then the current will flow through the ungrounded conductor,
No, it will flow through the grounded conductor.
> back to the source (usually a transformer), across the windings, and eventually back to the breaker that controls the circuit
The flow of power is the same via ground as it is via neutral.
> This will build up enough current (usually VERY fast, like milliseconds)
There is no such thing as "build up enough current", current does not "build up".
The milliseconds has to do with built in time delays at breakers, it's not a function of the electricity.
> The Earth has nothing to do with this
The actual Earth is used as a conductor, so yes, it definitely has something to do with this.
That would be a pretty good trick. The transformer is outside my house on a pole. Two wires run to it, the hot and the neutral. The "ground" doesn't leave the house. (Other wiring schemes exist, but this is standard USA residential.)
[EDIT: brainfart, see helpful correction below. still no "ground" at the pole...]
Yes there is. The neutral is bonded to ground, via an actual metal pole in the ground.
In your house is the same thing: The neutral (and the ground) and attached to a metal pole in the ground.
And the earth itself completes the circuit.
Standard US residential is 240V split phase, with two hot and one neutral conductor from the transformer. So three wires, minimum. Unless you have a very old feed.
I've seen houses where the earth wiring is completely independent and terminated in a metal rod buried outside. Seemed to be up to local code, breakers worked as they should.
The MBJ/SBJ is what bonds the neutral. This doesn't have anything to do with the Earth. This bonding has to be done anywhere between the origination of the circuit and the first overcurrent protective device.
The GEC is what connects to the Earth. This is used to stabilize voltage and to eliminate a difference in potential between metal parts during a high frequency event (like a nearby lightning strike or a transformer blowing up). This has nothing to do with the operation of breakers.
Edit to clarify: In principle, only the voltage difference between Live and Neutral matters for running a device. So theoretically one could construct a building supply where Neutral is not at earth potential. However, EGC has to be at earth potential, otherwise there would be a voltage between any metal electronic device and earthed objects, such as radiators or your feet standing in a puddle. This means that in practice both Neutral and EGC are always physically connected to the earth in some way and have to be for the system to work properly.
"The ONLY purpose for the EGC (or green wire) is to clear a ground-fault (clearing a ground-fault means tripping a breaker or blowing a fuse) in the 'oh shit moments'. It has absolutely NOTHING to do with the ground or the Earth and will work exactly as it is intended to regardless of whether it is connected to the Earth or not."
If the EGC is floating, no current will flow in a ground fault and the breaker never trips.