News for hackers. Stuff that matters.
Re:OVH Incident in Strasbourg by jbb67 on Thursday November 09, 2017 @04:29AM (#15661038)
When I've seen things like this before, it's often been the switchover hardware that fails, not the generator as such. it's much harder to test that as you don't want to tell your customers "sorry your sever went down, we were just testing if the switchover worked and it didn't"
Re:OVH Incident in Strasbourg by hinkley on Thursday November 09, 2017 @08:36AM (#15662195)
I worked for a company doing mostly on-premises (wireless) carrier software years back but they still wanted our own server room to be 3 nines for reasons lost to me now. They had installed new electrical circuits high on the walls so that we could survive minor flooding incidents.

So our lead Ops guy is unplugging half the redundant power supplies and plugging them into the new circuits, but a few critical servers are single PSU still, on UPS units. This is how he discovers that one of our PSUs has rotted and only has about five seconds of reserve power in it. Big outage, no bueno.

Re:OVH Incident in Strasbourg by vtsingaras on Thursday November 09, 2017 @05:25AM (#15661291)
Exactly that, we too suffered a power loss at our DC that was due to faults in the power supervising and switch-over circuits; we test both generators weekly.