But AWG24 cable also has a resistance of 0.08Ω/m (0.024Ω/ft). With a 10m (33ft) cable this amounts to (current has to travel both ways): R=2⋅ℓ=1.6 Ohms, at 3.5A this drops 5.6V. So, in the end you'd loose RI²=19.6W in the cable and only get 22.4W (3.5A at 6.4V) in the load...