Voltage drop is one way to look at it, but since efficiency is paramount, it's better to look at losses. Losses in the conductor are I^2 * R, so when there's a current of 3.5A, losses are 6.6W at an input of 3.5*13.4=46.9W. Efficiency is 88% which is very bad. An average inverter that converts the low DC voltage to AC is much more efficient and even with taking into account the wiring loss, there is a net gain. Generally, using a low voltage DC grid isn't a good idea.
Re:How to Get Your Apartment Off the Grid
by Scoundreller on Thursday May 19, 2016 @12:09AM
(#11727900)
Wouldn't there be 4 conductors, so resistance would be half when you pair them together?
Re:How to Get Your Apartment Off the Grid
by snowwindwaves on Thursday May 19, 2016 @02:02AM
(#11728319)
Yes.
But i forgot about the resistance from the load back to the source so above where I said 6m should actually be 3m. Or if two wires are parallel both from source to load and load back to source then we're back to 6m.
You could charge a phone, but even my small laptop chargers are over 60W. The big ones are 90W.
Also don't try this in your house! pushing 3.5A through that little pinner wire it could get hot and start a fire.