Re:OVH Incident in Strasbourg on Thursday November 09, 2017 @11:08AM (#15663520)
You can if you have to. But then you're really only doing a fancy simulation.

I accompanied my dad (power engineer) to a water purification plant where they were testing new equipment for the back up generator. There their weekly tests involved moving the entire plant to the diesel generator and running it of back up power for a couple of hours (once you start a big generator you have to let it run or it wont last long).

Potential problems for your generator that a resistor bank wont capture include, power factor (phase shift from a motor or switching supply), harmonics (from switching power), startup transients (from every power supplies' capacitors).

All these things can trip the generator, or worse, burn it out.

So if you can't test with the real load, supersize it!

P.S. Every test is a simulation of reality. At Fukushima the diesel generators flooded. Lesson - the unknown reason that'll knock out your grid can knock out your backup

P.P.S If you can, gently turning the load back on is very beneficial. Don't flip the master switch that controls all your load - flip a part of your load, wait a while for the system to stabilize, and flip part of it back.